19
Troubleshooting
Problem:
The StationMaster goes into shutdown mode when it should not.
Background:
When exiting programming mode the StationMaster turns on internal relays
to short circuit the track for a brief amount of time. During this time the power
entering the current sensor is measured. This is then stored as the “shutdown”
current. When the StationMaster detects this amount of current flowing thru
the track it will shut down assuming that there is a short circuit due to a derail,
mis-wire, etc. Sometimes a low shutdown value can be recorded if the
transformer is set to a low value during programming operations.
If the transformer throttle is then turned up while running the StationMaster could
sense an over-current and shut down.
Solution:
During programming mode turn the transformer throttle up to full speed.
To exit programming mode (as normal) turn the StationMaster dial fully clockwise
and allow the relays to click. At this time the true shutdown current is measured
and recorded. When the green LED starts flashing turn the transformer throttle back
down to the desired top speed of the train.
Problem:
The trains stops before reaching the ends.
Background:
The time to start decelerating is set by button #3 and retained in memory,
however the speed of the train could have changed due to a change in the
transformer throttle position, change of train engine, or change in programmed
acceleration or deceleration blinks.
Solution:
Any one of the following will allow the train to run farther before stopping:
1. Turn the top speed dial clockwise to increase the creep speed.
2. Turn up the transformer throttle.
3. Increase the programmed time delay to allow more creeping before reversing.
4. Change the START DECELERATION spot to be closer to the ends. (Press
button #1 to clear the programming for this direction and press button #3 again
to set the point where deceleration starts after the train reverses and comes
back.