Roth CM Manifold System
Installation Instructions
Roth Industries, Inc. 315-755-1011 e-mail - [email protected] www.roth-america.com
6
Mounting the manifold
Insert bottom ridge of manifold into bracket slots and twist into bracket until top ridge snaps into
brackets.
Orientation
The CM manifold can be mounted in any position, however the following conditions may occur
when manifolds are mounted in positions other than upright (loop tubing approaching from
bottom):
1. Upside down position (loop tubing approaching from above)
a.
Dirt may accumulate in the flow indicators over time. This will not have any effect on the
flow rate but may cause flow indicators to give false readings or stop working altogether.
b.
The flow indicators will indicate flow, however they will lose some of their precision in this
orientation. The flowmeter will indicate 20% less than actual flow.
c. Air vents must be inverted to operate as intended.
2. Vertical position (loop tubing approaching from either side)
a.
Dirt may accumulate in the flow indicators with the same effects as above.
b. The automatic air vent will not operate.
Caution: Conditions above do not qualify for warranty replacement.
Hardware
There are four mounting holes in the bracket set that will accommodate a 1/4” (6mm)
diameter fastener appropriate for the mounting surface material. These can include
wood screws, sheet metal screws or through-bolting as required.
Snap