Faults and malfunctions
43
FA ROTEX Solaris RPS3 25M - 03/2010
6
Faults and malfunctions
6.1
Display of events
Events occurring during operation can be displayed via the menu path: "Choice 2/2" -> "System" -> "Incidence memory" and
after entering the specialist password (see Section 5.3.4 and Image 5-5). For this purpose, the Solaris control unit contains a
simple fault diagnosis system. The incidence memory stores nature and time of the event. The event is displayed in plain text and
a code, the time since the event occurred is shown in hours. Starting with the most recent event, you can leaf through the
individual events by means of the Info key. If the "Delete" parameter in menu path: "Choice 2/2" -> "System" -> "Incidence
memory" is set at "Yes", all events will be deleted. Deletion of individual events is not possible. An overview of the possible entries
in the incidence memory can be found in Table 6 -1.
Event
code
Plain text
display
Description
Status
display
(flashes)
Light
(flashes)
Consequence
0
Collector Collector sensor: short circuit or break
K
TK
Permanent switch-off of P1 and optional P2
1
Return flow Return sensor: short circuit or break
R
TR
2
Storage tank Storage tank sensor: short circuit or break
S
TS
3
Flow
FlowSensor: short circuit or break
D
Operation without FlowSensor
4
Inflow
FlowSensor: short circuit or break
V
5
A/D
Internal A/D converter fault
G
Permanent switch-off of P1 and optional P2
6
Supply
Internal supply voltage fault
G
7
Reference Internal reference voltage fault
G
8
Reset
Overall reset was carried out
Parameters set to default values, calculated values
and event entries cleared (see Chapter 5.2.8), system
restarted
12
Start flow
Minimum flow rate V1 (see Table 5-1) was
not achieved in the start phase after "Time
P2" elapsed (see Chapters 5.2.1 and 5.2.10
for description)
W
P1 and optional P2 switched off for 2 h, after that,
ready for operation again or Status "F"
F
TV
P1 and optional P2 switched off permanently if event
occurs three times in succession without successful
start in the intervening period.
13
TS > Tmax
Maximum storage tank temperature ("T
S
max") exceeded (see Chapters 5.2.1 and 6.2
for description)
TS
Temporary switch-off of P1 and
optional P2
14
TR >> TS
T
R
- T
S
> 10 K and TR > 40 °C
(see Chapter 6.2 for description)
TR
15
TK >
TK perm
Maximum permissible collector temperature
("T
K
perm") exceeded - (see Chapters 5.2.1
and 6.2 for description)
TK
16
Interrupt
Interruption in flow detected during operat-
ing phase (V < V2, see Chapter 5.2.8 and
Table 5-1)
Temporary switch-off of P1 and optional P2 (at least
for stabilisation time), refilling by P1 and optional P2
for "Time P2" at next switch-on condition.
202
P-on reset Switch on
Restart, all parameter settings and info parameters
remain valid.
204
Brown-out
Reset due to impermissible reduction in mains
voltage
Restart according to Code 202.
205
Watchdog
Reset due to external disturbances (e. g.,
overvoltage caused by thunderstorms)
Restart according to Code 202.
Table 6 -1
Incidence memory