7
INSTALLATION
Setting up and adjusting
After checking the supply pressure, it is necessary to adjust the pressure at the nozzle, proceeding
as described below:
1. Make sure the gas supply as been cut off.
2. Take off the door by unscrewing the screw fixing it to the support.
3. Remove the water loading knob (1 di fig. 3) and unscrew the two screws fixing the instrument
panel to the under-panel. Remove the instrument panel taking care over the wire of the igniter.
4. Open the gas inception cock and ignite the burner flame by following the instructions of par 5.2
positioning the knob onto the maximum position.
5. Adjust the pressure regulator since the manifold pressure is 4” W.C.
6. Operate the appliance in the maximum conditions for at least 15 minutes, and then turn the
knob onto the minimum position.
7. Turn the minimum adjustment screw (pos. a in fig. 7) to obtain a reduced flame but sufficiently
stable and homogeneous.
8. Turn off the burner by following the instructions of par. 5.2, close the gas interception cock,
disconnect the pressure gauge, screw the closing screw back and refit the instrument panel
and the front door.
2.4.2 Checks
For the purposes of operating safety it is essential to make the following checks:
*
Checking air-tightness:
Check there are no leaks in gas pipe using a solution of soap water.
*
Checking operation:
Check the burner, the regularity and extinguishing of the flame, following
the instructions in this handbook.
*
Checking the flue gas evacuation system:
Make sure there is a functional flue gas evacuation
system.