Filling the Foam Compound Tank
ATTENTION !
Before beginning foam compound tank filling ensure that the drain
valve is closed.
Always provide the foam compound tank fill/drain connection
(J63) with a blind coupling.
Please take care that the foam tank must be drained completely as
soon as the brand of foam compound is changed.
Furthermore the foam proportioning systems must be flushed and
cleaned before refilling the foam compound tank - please refer to
the "Flushing after Foam Operation" chapter.
Filling the Foam Compound Tank
Filling the foam compound tank with an external foam compound
pump
- Connect the supply hose (foam compound) to the fill connection
(J63) located below the left locker compartment.
- Engage the external foam compound pump (please refer to the
operation manual of the foam compound pump manufacturer).
- Open the foam compound tank fill valve (J62).
- Check the foam tank level gauge (P2) during filling or open
foam tank cover to watch the rise and stop filling on time.
◊
The pilot lamp (H108) illuminates as long as the foam
compound tank content is less than one third.
- When the foam compound tank is full close the valve (J63).
- Stop delivery of foam compound and uncouple the hose.
Note:
The foam compound tank can also be drained by means of connec-
tion (J63) and the valve (J62). Provide a suitable collecting
container.