Page - 92 -
FLF 15000/1800/500
Panther 8x8 CA-7
© 2014
Emergency operation of a single pneumatic actuator
The water tank suction valve, the foam compound tank suction
valve and the roof turret valve as well as the left and right regulated
discharge valves* can be separately disconnected from the pneu-
matic system.
After that each valve can be operated by using the emergency tool
(90).
Procedure:
Close valve (J168/1) and operate the water tank suction valve drive
(Z28) by using the emergency tool.
Close valve (J168/2) and operate the foam compound tank suction
valve drive (Z61) by using the emergency tool.
Pneumatic Installation
Emergency Control of Pneumatic Actuators
In case compressed air is not available, or a solenoid fails the
pneumatic actuators can be operated manually to open or close
the valve concerned.
Procedure:
- Close shut-off-valve (J163).
◊
Pressure is released from the pumps pneumatic system.
- Put emergency tool on drive of pneumatic actuator.
- Turn emergency tool by 90
°
clockwise to operate valve.
Note:
After closing the shut-off valve (J163), all pneumatic
actuators must be operated manually.
The pneumatic system has to be repaired immediately after use.
CAUTION !
Before opening the pressure supply, make sure that the emergency
tool is removed from the valve-drive - danger of jamming!
J168/1
J163
J168/2
Z61
Z28
90