![Rosemount 702 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/rosemount/702/702_reference-manual_1487401028.webp)
Reference Manual
00809-0200-4702, Rev BA
June 2010
Rosemount 702
3-8
Figure 3-11. Fuel Sensor wiring
NOTE
All part numbers on this page refer to products sold by Tyco Thermo Controls,
LLC.
•
The Emerson Smart Wireless 702 Discrete Transmitter can support up
to 500 feet of TraceTek hydrocarbon or solvent sensor cable (TT5000
or TT5001 series). The total amount of sensor cable connected to a
single 702 transmitter is not to exceed 500 ft. However leader cable,
jumper cables (if used) and branch connectors are not included in the
500 foot limit. See Figure 3-12 for typical configurations.
Figure 3-12. Fuel Sensor sensor
cable wiring
TT-MLC-MC-BLK (Leader Cable)
TT-FFS-100 or TT-FFS-250
(Fast Fuel Sensor Probe)
TT-MLC-MC-BLK (Leader Cable)
TT-FFS-100 or TT-FFS-250
(Fast Fuel Sensor Probe)
TT-ZBC-xx-MC-BLK
(Branch Connector)
TT-MJC-xx-MC-BLK (Optional Jumper Cable)
TT-MLC-MC-BLK (Leader Cable)
TT5000/TT5001 Sensor Cable
(up to 500 ft.)
TT-MET-MC (End Termination)
TT-MJC-xx-MC-BLK (Optional Jumper Cable)
TT-ZBC-xx-MC-BLK
(Branch Connector)
TT-MET-MC
(End Termination)
Up to 500 ft. TT5000 or TT5001
sensor cable
(Total per 702)
TT-MET-MC
(End Termination)
Содержание 702
Страница 2: ......
Страница 12: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 1 6 ...
Страница 20: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 2 8 ...
Страница 34: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 4 4 ...
Страница 56: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 A 6 ...
Страница 64: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 B 8 ...
Страница 66: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 Index 2 ...
Страница 67: ......