Reference Manual
00809-0200-4702, Rev BA
June 2010
3-7
Rosemount 702
Liquid Hydrocarbon
Detection, Measurement
Option Code 61
Figure 3-9. Fuel Sensor
Terminal
The Liquid Hydrocarbon Detection configuration is intended for use with the
Tyco
®
TraceTek
®
Fast Fuel Sensor, or TraceTek sensing cable.
Figure 3-10. Fuel Sensor
Connection
The connections to the Fast Fuel Sensor TraceTek sensing cable are made
by matching the appropriately colored wires to the matching colored
termination lugs.
•
The Emerson Smart Wireless 702 Discrete Transmitter can support up
to 3 Fast Fuel sensors. These Fast Fuel sensors are connected using
TraceTek Modular Leader Cable (TT-MLC-MC-BLK), optional modular
jumper cables (TT-MJC-xx-MC-BLK) and branching connectors
(TT-ZBC-MC-BLK) as suggested in Figure 3-11.
•
If more than one Tyco Fast Fuel sensor is attached to a 702 transmitter,
the detection of liquid hydrocarbon by one sensor is sufficient to cause
the 702 to send a “Leak” message. However, it is not possible for the
702 to discern which individual sensor has detected liquid hydrocarbon.
Содержание 702
Страница 2: ......
Страница 12: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 1 6 ...
Страница 20: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 2 8 ...
Страница 34: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 4 4 ...
Страница 56: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 A 6 ...
Страница 64: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 B 8 ...
Страница 66: ...Reference Manual 00809 0200 4702 Rev BA June 2010 Rosemount 702 Index 2 ...
Страница 67: ......