September 2016
24
Quick Start Guide
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress protection of the enclosure to at
least IP66/68.
2. Unused cable entries must be filled with suitable blanking plugs which maintain the
ingress protection of the enclosure to at least IP66/68.
3. Cable entries and blanking plugs must be suitable for the ambient range of the
apparatus and capable of withstanding a 7J impact test.
N7
IECEx Type n
Certificate: IECEx BAS 13.0111X
Standards: IEC 60079-0:2011, IEC 60079-15: 2010
Markings: Ex nA IIC T5 Gc (-40 °C
≤
T
a
≤
+70 °C)
Special Condition for Safe Use (X):
1. The Model 4088 MV Transmitters fitted with transient protection are not capable of
withstanding the 500V test as defined in Clause 6.5.1 of IEC 60079-15:2010. This must
be taken into account during installation.
Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 15.0531X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-1:2009 +
Errata 1:2011, ABNT NBR IEC60079-26:2008 + Errata 1:2008
Markings: Ex d IIC T6…T4 Ga/Gb, T6(-50 °C
≤
T
a
≤
+65 °C), T5/T4(-50 °C
≤
T
a
≤
+80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm. Installation, maintenance and use shall take
into account the environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall be followed in
detail to assure safety during its expected lifetime.
2. In case of repair, contact the manufacturer for information on the dimensions of the
flameproof joints.
3. Appropriate cable, glands, and plugs need to be suitable for a temperature of 5 °C
greater than the maximum specified temperature for the location where it is installed.
4. The transmitter can be installed in the boundary wall between an area of EPL Ga and the
less hazardous area, EPL Gb. In this configuration, the process connection is installed in
EPL Ga, while the transmitter housing is installed in EPL Gb.
5. The applicable temperature class, ambient temperature range and process temperature
range of the equipment is as follows:
T4 for –50 °C
≤
T
a
≤
80 °C with T process = –50 °C to 120 °C
T5 for –50 °C
≤
T
a
≤
80 °C with T process = –50 °C to 80 °C
T6 for –50 °C
≤
T
a
≤
65 °C with T process = –50 °C to 65 °C
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 15.0720X
Standards: ABNT NBR IEC60079-0:2008 + Errata 1:2011, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIB T4 Ga, T4(-60 °C
≤
T
a
≤
+70 °C)
Содержание 4088A MultiVariable
Страница 26: ...September 2016 26 Quick Start Guide Figure 16 Rosemount 4088 Declaration of Conformity ...
Страница 27: ...Quick Start Guide 27 September 2016 ...
Страница 28: ...September 2016 28 Quick Start Guide ...
Страница 29: ...Quick Start Guide 29 September 2016 ...
Страница 31: ...Quick Start Guide 31 September 2016 ...