16
Quick Start Guide
Figure 15. Configuration via RS-485 Network Port
The Rosemount 4088 may be configured with the Rosemount 3095FB
Configuration Software. When using this legacy tool, only functionality that was
available with the Rosemount 3095FB can be accessed. The device must be
removed from the Modbus
®
network prior to communicating over the RS-485
bus.
Note
Device configuration procedures are given for RTIS in the Rosemount 4088 MultiVariable
Transmitter
Reference Manual
. This manual also includes a detailed Modbus register map.
A check (
) indicates the basic configuration parameters. At a minimum, these
parameters should be verified as part of the configuration and startup procedure.
A. RS- 485 (A)
B. RS-485 (B)
C. RS-485 bus, twisted pair required
D. Bus Termination: AC Termination on 4088 (see
“Set
the switches” on page 9
) or 120
resistor
E. User-provided power supply
F. Rosemount 3095FB
configuration software
G. RS-232/RS485 converter
Table 3. Fast Keys
Category
Function
Fast Key sequence
Device
Available Measurements
1,9,4
Device
Display
2,2,5
Device
Sensor Module Temperature
2,2,4
Device
Sensor Module Temperature Units
2,2,4,3
D
C
B
A
D
E
F
G
Ω