Reference Manual
00809-0100-4825, Rev BB
August 2005
A-5
Rosemount 248
Transmitter Accuracy and Ambient Temperature Effects
NOTE
The accuracy and ambient temperature effect is the greater of the fixed and
percent of span values (see example below).
Table A-2. Rosemount 248 Transmitter Input Options, Accuracy, and Ambient Temperature Effects
Transmitter Accuracy Example
When using a Pt 100 (a = 0.00385) sensor input with a 0 to 100 °C span:
Accuracy would be ±0.2 °C.
Transmitter Temperature Effects Example
Transmitters can be installed in locations where the ambient temperature is
between –40 and 85 °C (–40 and 185 °F). In order to maintain excellent
accuracy performance, each transmitter is individually characterized over this
ambient temperature range at the factory.
When using a Pt 100 (
α
= 0.00385) sensor input with a 0-100 °C span at 30
°C ambient temperature-Temperature Effects: 0.006 °C x (30 - 20) = 0.06 °C
Total Transmitter Error
Worst Case Transmitter Error: Ac Temperature Effects = 0.2 °C +
0.06 °C = 0.26 °C
Total Probable Transmitter Error:
Sensor
Transmitter Input Ranges
Accuracy
Temperature Effects per 1.0 °C (1.8 °C)
Change in Ambient Temperature
(1)
(1) Change in ambient is with reference to the calibration temperature of the transmitter (68 °F (20 °C) from factory.
°C
°F
Fixed
% of Span
Fixed
% of Span
2-, 3-, 4-wire RTDs
Pt 100
(2)
(
α
= 0.00385)
(2) IEC 751, 1995
–200 to 850
–328 to 1562
0.2 °C (0.36 °F)
±0.1
0.006 °C (0.011 °F)
±0.004
Pt 100
(3)
(
α
= 0.003916)
(3) JIS 1604, 1981
–200 to 645
–328 to 1193
0.2 °C (0.36 °F)
±0.1
0.006 °C (0.011 °F)
±0.004
Pt 200
(2)
–200 to 850
–328 to 1562
1.17 °C (2.11 °F)
±0.1
0.018 °C (0.032 °F)
±0.004
Pt 500
(2)
–200 to 850
–328 to 1562
0.47 °C (0.85 °F)
±0.1
0.018 °C (0.032 °F)
±0.004
Pt 1000
(2)
–200 to 300
–328 to 572
0.23 °C (0.41 °F)
±0.1
0.010 °C (0.018 °F)
±0.004
Ni 120
(4)
(4) Edison Curve No. 7
–70 to 300
–94 to 572
0.16 °C (0.29 °F)
±0.1
0.004 °C (0.007 °F)
±0.004
Cu 10
(5)
(5) Edison Copper Winding No. 15
–50 to 250
–58 to 482
2 °C (3.60 °F)
±0.1
0.06 °C (0.108 °F)
±0.004
Thermocouples
(6)
(6) Total accuracy for thermocouple measurement: sum of ac0.5 °C.
Type B
(7)
(7) NIST Monograph 175, IEC 584
100 to 1820
212 to 3308
1.5 °C (2.70 °F)
±0.1
0.056 °C (0.101 °F)
±0.004
Type E
(7)
–50 to 1000
–58 to 1832
0.4 °C (0.72 °F)
±0.1
0.016 °C (0.029 °F)
±0.004
Type J
(7)
–180 to 760
–292 to 1400
0.5 °C (0.90 °F)
±0.1
0.016 °C (0.029 °F)
±0.004
Type K
(7)
–180 to 1372
–292 to 2502
0.5 °C (0.90 °F)
±0.1
0.02 °C (0.036 °F)
±0.004
Type N
(7)
–200 to 1300
–328 to 2372
0.8 °C (1.44 °F)
±0.1
0.02 °C (0.036 °F)
±0.004
Type R
(7)
0 to 1768
32 to 3214
1.2 °C (2.16 °F)
±0.1
0.06 °C (0.108 °F)
±0.004
Type S
(7)
0 to 1768
32 to 3214
1 °C (1.80 °F)
±0.1
0.06 °C (0.108 °F)
±0.004
Type T
(7)
–200 to 400
–328 to 752
0.5 °C (0.90 °F)
±0.1
0.02 °C (0.036 °F)
±0.004
DIN Type L
(8)
(8) DIN 43710
–200 to 900
–328 to 1652
0.7 °C (1.26 °F)
±0.1
0.022 °C (0.040 °F)
±0.004
DIN Type U
(8)
–200 to 600
–328 to 1112
0.7 °C (1.26 °F)
±0.1
0.026 °C (0.047 °F)
±0.004
Type W5Re/W26Re
(9)
(9) ASTME 988-96
0 to 2000
32 to 3632
1.4 °C (2.52 °F)
±0.1
0.064 °C (0.115°F)
±0.004
Millivolt Input
–10 to 100 mV
0.03 mV
±0.1
0.001 mV
±0.004
2-, 3-, 4-wire Ohm Input
0 to 2000 ohms
0.7 ohm
±0.1
0.028 ohm
±0.004
0.2
2
0.06
2
+
0.21
°
C
=
Содержание 248
Страница 2: ......
Страница 4: ......
Страница 46: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 4 8 ...
Страница 64: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 A 18 ...
Страница 74: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 B 10 ...
Страница 77: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 1 Rosemount 248 NOTES ...
Страница 78: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 0 2 NOTES ...
Страница 79: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 3 Rosemount 248 NOTES ...