USB Field Upgrade Procedure
Procedure to field upgrade Rooster
TM
Sensor100
Operating System
You will need: USB thumb drive with new firmware
“
Rooster
.bin”
Rooster
TM
Sensor100
Procedure:
1.
Remove power from the Rooster
TM
Sensor100 by unplugging power supply.
2.
Insert USB thumb drive into left side of Rooster
TM
Sensor100.
3.
Depress and hold
“Home”
button, then re-apply power to your unit.
(Hard Home button must be
depressed while Rooster
TM
powers up to enter the firmware update sequence)
4.
After ~3 seconds, release Home button. After 10 seconds, the LED on the front of the Rooster
TM
will light and the unit will boot up with new Firmware.
5.
When you have completed the Factory Reset Procedure, navigate to the info [
] screen from
home to validate that your new firmware version was properly installed. The date of the firmware
release
–
listed next to “firmware”
- should have changed to the most current build. If this is not
the case, repeat steps 1-6 again.
Factory Reset Procedure
The Master Reset will return the Rooster Sensor100 to its default alarm & input/output settings. Time and
date will be preserved during a factory reset. The following Factory Reset Procedure can be done at any
time upon system reset to restore default settings and passwords.
1.
After following the above steps, when the 1
st
information screen displays, momentarily press the
“Mute” key
.
2.
The “Enter Factory Password” screen will display. Factory Password is “
5878
” and cannot be
changed.
3.
Factory Menu will display. Depr
ess “Reset to Factory Defaults”
Factory-default c
ertify password is “
6425
”