Rooster
™
Sensor100 USER MANUAL 62320MN000-A02
Rooster
TM
Sensor100 USER MANUAL 62320MN000-A02
13
Startup Delay
The startup delay prevents an alarm from triggering until the workstation and ventilation systems have fully
powered up and are operational. Refer to chart on next page for further definitions.
Alarm Delay
Definition
30s
Alarm is paused for 30 seconds on power up.
1 min
Alarm is paused for 1 minute on power up.
2 min
Alarm is paused for 2 minutes on power up.
5 min
Alarm is paused for 5 minutes on power up.
Duct Size
Volumetric flow can be displayed on the home screen for the
Rooster
TM
Sensor100. In order to set this up, enter the duct
diameter screen from the settings menu. Select the shape of
the duct, and the diameter (in cm).
Once the duct diameter is entered, the user is then able to
cycle between fpm, m/s, and cfm on the home screen.
Home>Settings>Duct Size
Airflow Resolution
For advanced users, displayed velocity units can be configured to display in an alternate resolution.
The default resolution for units is 1 fpm and .01 m/s respectively, however, for users who prefer a more
uniform readout, this can be configured up to 5 fpm or .05 m/s.
Home>Settings>System>Airflow Settings>Airflow Resolution
Airflow Resolution Definition
1 fpm
Displayed units in FPM are rounded to 1 fpm. This is the default setting.
2 fpm
Displayed units in FPM are rounded to 2 fpm.
5 fpm
Displayed units in FPM are rounded to 5 fpm.
.01 m/s
Displayed units in m/s are rounded to .01 m/s. This is the default setting.
.02 m/s
Displayed units in m/s are rounded to .02 m/s.
.05 m/s
Displayed units in m/s are rounded to .05 m/s.
Airflow Sensitivity
This setting smooths airflow readings by applying a filter that determines “sensitivity” of readings.
Home>Settings>System>Airflow Settings>Sensitivity
Sensitivity
Definition
Low
Decreases filtration effect, resulting in greater fluctuation of readings.
Med
Default setting. Filtration effect stabilizes readings.
High
Increases filtration effect, providing smoother readings.