background image

Ronk Vigilant

®

 Owner’s and Installation Manual

 

9

VIGILANT

®

 PRODUCT SERIES

Vigilant

®

 Product Overview

Ronk Vigilant

®

 series automatic transfer switches are represented 

by the VTS product identifier designed with all required sensing 
circuitry provided. The sensing circuitry allows automatic transfer 
of an electrical load to a standby power source in the event of an 
over/under voltage or frequency condition on any or all phases of 
the utility power source. Upon the restoration of the utility supply, 
the electrical load will be automatically retransferred to the utility 
power source. 
All Vigilant

®

 transfer switch mechanisms incorporate a double-

throw action switching device for automatic transferring. The 
Vigilant

®

 transfer switch mechanism is a contactor-operated 

device controlled by a set of utility and generator solenoids. 
Manual operation is also provided for manual transfer of the load 
between the power sources if necessary.

 

Figure 2 – Vigilant

®

 Series

Receiving, Handling and Storage

Shipment contents:

• 

Vigilant

®

 Series – Automatic Transfer Switch

• 

Installation and User Manual

• 

Warranty card

Receiving 

Every effort is made to ensure that your Vigilant

®

 transfer switch 

arrives at its destination undamaged and ready for installation. 
The packing is designed to protect the transfer switch’s internal 
components as well as the enclosure. Care should be taken to 
protect the equipment from impact at all times. Do not remove the 
protective packaging until the equipment is at the installation site 
and ready to be installed.
After unpacking, inspect the switch for any damage that may 
have occurred during shipping. If any missing parts or damage is 
discovered when unpacking, do not return the unit to the place of 
purchase; please contact Ronk Electrical for instructions on how 
to proceed. Never install a switch that has been damaged.
A shipping label affixed to the shipping box includes a variety of 
product and shipping information, such as items and customer 
numbers. Make certain that this information matches your order 
information.

Handling

As previously mentioned, each Vigilant

®

 transfer switch is 

packaged in its own individual box. Protect the equipment from 
impact at all times and do not double stack. Once the transfer 
switch is at the installation site and ready to be installed, the 
packaging material may be removed.

Storage

Although well packaged, this equipment is not suitable for 
outdoor storage. If the transfer switch is to be stored indoors 
for any period of time, it should be stored with its protective 
packaging in place. Protect the transfer switch at all times 
from excessive moisture, dirty conditions, corrosive conditions 
and other contaminants. It is strongly recommended that the 
package-protected equipment be stored in a climate-controlled 
environment of -4° to 149°F (-20° to 65°C), with a relative 
humidity of 80% or less. Do not stack other equipment on top of 
the stored switches.

Содержание VIGILANT Series

Страница 1: ...OWNER S INSTALLATION MANUAL MODEL VTS01001240SX VTS02001240SX 100 200 AMP ELECTRICAL INDUSTRIES INC...

Страница 2: ...plain and or exemplify a product service or maintenance improvement We reserve the right to make any change at any time without notice Some images may vary depending upon which model is shown ALL RIGH...

Страница 3: ...Catalog Number Identification 10 INSTALLATION AND WIRING 11 General Information 11 Mounting Location 11 Mounting Requirements 11 Recommended Upstream Protection 11 Power Connections 12 Lug Torque Val...

Страница 4: ...22 Engine Exerciser and External LED Annunciation 22 Introduction 22 Clearing the Exerciser 23 Set Current Time and Date 23 Set Program Timing 23 Program Review 23 ON AUTO OFF Mode 23 WARRANTY 24 Vigi...

Страница 5: ...ocedures Only licensed electrical contractors should install an ATS Installations must comply completely with all federal state and local codes standards and regulations Your installer should follow t...

Страница 6: ...zardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates a...

Страница 7: ...ot touch bare wires Do not use equipment with worn frayed bare or otherwise damaged wiring Do not handle electrical cords while standing in water while barefoot or while hands or feet are wet If you m...

Страница 8: ...00V DC TP J2 4 Normal Line Sensing Under Voltage Dropout 11 18 Pickup 6 13 2 accuracy Dropout 18 Pickup 13 2 accuracy Normal Line Sensing Under Frequency 5 12 1 accuracy 12 1 accuracy Emergency Line...

Страница 9: ...be taken to protect the equipment from impact at all times Do not remove the protective packaging until the equipment is at the installation site and ready to be installed After unpacking inspect the...

Страница 10: ...10 Ronk Vigilant Owner s and Installation Manual VIGILANT PRODUCT SERIES Vigilant Catalog Number Identification Figure 3 Figure 4...

Страница 11: ...sult in a system malfunction Mounting Requirements The enclosure has a NEMA National Electrical Manufacturer s Association type 3R rating and is suitable for indoor outdoor installations and provides...

Страница 12: ...lues as shown in Table 1 and Table 2 WARNING Low voltage wire cannot be installed in the same conduit as power voltage wiring It could result in shock due to short circuit as well as cause electromagn...

Страница 13: ...e an isolated power supply to power the controller as the controller requires a reference to neutral for AC sensing which it obtains from the distribution system via Battery RSC1 and RSC2 need to be c...

Страница 14: ...time delay has expired the remote contacts will close sending a signal to the generator s automatic start controller When the control board senses that the generator has started and is within accepta...

Страница 15: ...a 12 OR 24 VDC system voltage In 12VDC system operation the controller requires that jumpers be installed in the 12 24VDC jumper location In 24VDC system operation the controller requires that no jump...

Страница 16: ...3 Weekly exercise with load no load ON Load test cycle OFF No load test cycle 4 Set the over under voltage setting OFF Dropout v 18 Pickup v 13 OFF Dropout v 17 Pickup v 12 OFF Dropout v 16 Pickup v...

Страница 17: ...to run under a no load condition until the engine cool time delay has expired TDES Time Delay Engine Start This delay prevents unnecessary engine starts When the control board determines a utility fai...

Страница 18: ...h will allow remote testing of the transfer switch The purpose of the test switch is to simulate a utility power failure The remote test switch may be installed by a licensed electrical contractor the...

Страница 19: ...ase note the flat side of the removable handle must face away from the power connection side of the switch mechanism as seen in Figure 12 for easy transferring Always remove the handle from the manual...

Страница 20: ...tion for possible safety hazards Inspect mounting location for any safety or fire hazards Inspect for dirt wiring damage and mechanical damage Inspect the transfer switch for loose hardware Check all...

Страница 21: ...Wiring Diagram MATERIAL FINISH TITLE VIGILANT 100A 200AATS 2000 SERIES WIRING DIAGRAM 2 POLE 240V SCALE NTS REVISIONS 12 22 14 NEW ECO 031024 DEF E BL E CONSOLIDATED TERMINATIONS FOR NEW VENDOR 2 2 1...

Страница 22: ...ity of the transfer switch system The exact day and time may be specified for testing External LED indication is available for utility available generator NEMA 3 available transfer to utility transfer...

Страница 23: ...TE Unused ON and OFF times must have dashes not zeros The time of day is displayed in the 24 hour notation so 00 00 is midnight Program Review 1 Repeatedly press TIMER button to advance the display to...

Страница 24: ...ot be appropriate or applicable For example warranty service would not apply if equipment damage occurred because of misuse lack of routine maintenance shipping handling warehousing or improper instal...

Страница 25: ...Ronk Vigilant Owner s and Installation Manual 25 NOTES...

Страница 26: ...26 Ronk Vigilant Owner s and Installation Manual NOTES...

Страница 27: ...Ronk Vigilant Owner s and Installation Manual 27 NOTES...

Страница 28: ...RONK PO Box 160 106 East State Street Nokomis IL 62075 0160 Toll Free 800 221 7665 ronkelectrical com UG 001 02 1 2020...

Отзывы: