background image

CPR32-SE-BRD v3.0 User Manual

 

2020-10-08 

 

 

14/15 

 

to place FDM jumper  in order  to put  the device in firmware download  mode. Therefore firmware 

update can be performed by means of RS485 bus of access control system. 

Firmware update procedure 

 

 Place jumper on FDM pins – see fig. 1 

 

 Reset device (press RST button or switch power off/on) 

 

 Start RogerISP software and select communication port (in case of RUD-1 select 

USB-RS485 

Converter

). 

 

Press the button 

Erase

 

 

Once more reset the device (place and remove jumper on RST pins or switch power off/on) 

 

 In  Firmware  window  select  firmware  *.hex  file  (can  be  downloaded  from  www.roger.pl)  and 
then select the button 

Program

 

 

After  firmware  upload  remove  jumper  from  FDM  pins  and  reset  device  (press  RST  button  or 
switch power off/on) 

Note: If the CPR is not responding after firmware update procedure then it is necessary to perform 
reset – see 4.2 Memory Reset or update the firmware once more. 
 

Note: In case of network system, it is required to upload full configuration to the system after CPR 
firmware update. 

4.4 Problem with erratic jumps of mouse cursor in Windows OS 

Occasionally, when RACS 4 system is equipped with CPR32-SE-BRD network controller connected to 
PC through such serial interfaces as UT-2USB, RUD-1 or UT-4 with virtual serial port then CPR is 

erroneously detected by Windows as Microsoft Serial Ball Point device. In such case mouse cursor 
goes crazy (erratically jumps around screen) and PR Master software reports serial port error.  

Note: The problem, which is described above is not caused by CPR32-SE-BRD but it results from 
commonly known Windows fault and it cannot be corrected by Roger engineers. 

Manual disabling of detected device in Device Manager 

 

After Windows loading and occurrence of problem with mouse cursor, turn the CPR32-SE-BRD 
off. 

 

Open Device Manager in Windows operating system. 

 

In the Device Manager click Mice and other pointing devices. 

 

Right click Microsoft Serial Ball Point and select Disable from menu. 

 

Close Device Manager. 

 

Turn CPR32-SE-BRD on. 

The method might not resolve the problem permanently.  Therefore you may consider to uninstall 
Microsoft Serial Ball Point device in Device Manager if it does not affect normal use of your PC. 

5.

 

O

RDERING INFORMATION

 

Table 7.Ordering information 

CPR32-SE-BRD v3.0  Electronic module of network controller. 

UT-4DR 

Ethernet-RS485 communication interface. 

UT-2USB 

USB-RS485 communication interface. 

RUD-1 

Portable USB-RS485 communication interface with 12VDC/0.12A output. 

 

 
 

Содержание CPR32-SE-BRD

Страница 1: ...version 3 0 5133 or newer Hardware version 3 0 Document version Rev B 2016 ROGER sp z o o sp k All rights reserved This document is subject to the Terms of Use in their current version published at th...

Страница 2: ...3 3 Power supply 6 3 4 Communication with CPR 8 3 5 Input and output lines 8 3 5 1 Inputs 8 3 5 2 Relay outputs 8 3 5 3 General purpose outputs 8 3 6 Installation guidelines 9 4 Configuration 9 4 1 C...

Страница 3: ...erns PRxx1 series controllers The network controller is equipped with RS485 port which is used for direct communication with access controllers and for communication with computer PR Master software u...

Страница 4: ...IN8 input line P2 Power supply for CPR IO1 IO1 output line COM REL1 relay common terminal IO2 IO2 output line NC REL1 relay output NC IN1 IN1 input line NO REL1 relay output NO IN2 IN2 input line CLK...

Страница 5: ...CPR32 SE BRD v3 0 User Manual 2020 10 08 5 15 Fig 2 Typical connection diagram for CPR32 SE BRD v3 0 network controller...

Страница 6: ...roller is designed for power supply from 230VAC 18VAC transformer with minimal power output 25VA but it can also be supplied with 12VDC The connection of power supply is shown in fig 4 and fig 5 If CP...

Страница 7: ...CPR32 SE BRD v3 0 User Manual 2020 10 08 7 15 Fig 4 CPR32 SE BRD v3 0 and PR402DR PR411DR controllers supplied with 18VAC Fig 5 CPR32 SE BRD v3 0 and PRxx1 PRxx2 series controllers supplied with 12VDC...

Страница 8: ...istors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc b...

Страница 9: ...n bus including connected access controllers CPR32 SE BRD network controller and communication interface e g UT 2USB the installer can proceed with installation and configuration of PR Master software...

Страница 10: ...CPR off and on Menu Settings Inputs Outputs In the window opened by means of this option it is possible to assign functions to CPR32 SE BRD inputs and outputs Additionally in case of inputs the admin...

Страница 11: ...ed at all controllers doors within subsystem network 12 Clear all alarms in subsystem ON monitored When the input is activated then all alarms in CPR32 SE BRD and controllers within particular subsyst...

Страница 12: ...es controllers within the subsystem network 73 Alarm in CPR The output is activated for 3 minutes if Tamper Alarm or Power supply alarm is raised The function 67 operates as a sum of 81 and 82 functio...

Страница 13: ...ut is activated for 3 minutes when the event memory buffer is filled in 75 90 Low battery 3 min The output remains activated for 3 minutes if charge level of backup battery connected to CPR32 SE BRD u...

Страница 14: ...d with CPR32 SE BRD network controller connected to PC through such serial interfaces as UT 2USB RUD 1 or UT 4 with virtual serial port then CPR is erroneously detected by Windows as Microsoft Serial...

Страница 15: ...have a negative impact on the environment and health The user is obliged to deliver equipment to the designated collection points of electric and electronic waste For detailed information on recycling...

Отзывы: