CPR32-SE-BRD v3.0 User Manual
2020-10-08
13/15
[81]
Tamper alarm
The output is activated for 3 minutes if anti-sabotage
(tamper) alarm is raised. The alarm is raised when the input
with function [02] is activated.
[82]
Power supply alarm
The output is activated for 3 minutes if problem with CPR32-
SE-BRD power supply occurs. The function [82] is a sum of
[74], [75] and [76] functions.
[83]
Communication lost
The output is activated as long as the communication with
any PR series controller within particular subsystem
(network) is lost.
[84]
Buffer alarm
The output is activated when the event memory buffer is full
and remains activated until the buffer is cleared.
[85]
Buffer prealarm
The output is activated when the event memory buffer is
filled in 75%.
[86]
Internal failure
(3 min)
The output is activated for 3 minutes when internal testing
detects RTC failure, firmware memory failure or data
memory error. Internal test is started every 20 minutes.
[87]
Communication lost
(3 min)
The output is activated for 3 minutes if the communication
with any PR series controller within particular subsystem
(network) is lost.
[88]
Buffer alarm (3 min)
The output is activated for 3 minutes when the event
memory buffer is full.
[89]
Buffer prealarm
(3 min)
The output is activated for 3 minutes when the event
memory buffer is filled in 75%.
[90]
Low battery (3 min)
The output remains activated for 3 minutes if charge level of
backup battery connected to CPR32-SE-BRD unit is low.
[91]
18VAC supply lost
(3 min)
The output is activated for 3 minutes after 15 minutes of
18VAC power supply shortage to CPR32-SE-BRD unit.
[92]
Battery failure
(3 min)
The output is activated for 3 minutes in case of battery
failure (no battery or internal damage of battery). If the
output is activated then the battery must be controlled by
maintenance personnel.
[93]
Zone Armed
The output is activated as long as associated alarm zone is
armed.
4.2 Memory Reset
Memory Reset procedure erases current settings and restores default factory settings. After
Memory Reset procedure the CPR automatically enters normal working mode.
Place jumper on 1 pins – see fig. 1
Reset device (press RST button or switch power off/on)
Remove jumper from 1 pins
After a few seconds the CPR shall restart automatically and switch to normal mode
4.3 Firmware update
The latest versions of firmware and Roger ISP software are available at
. In order to
update firmware it is necessary to connect the device by means of RS485 bus to communication
interface (UT-2USB or RUD-1) and then connect the interface to PC with installed Roger ISP
software. It is not necessary to disconnect the CPR from access control system, it is only required