EN
66
CONTACT
DESCRIPTION
18(COM)-19(LNA)-20(LNB)
CO
M
LNA
LNB
18 19 20
Function.
Serial communication enables synchronised operation of the two barriers.
The obstacle detection system immediately reverses the direction of the boom which detected the obsta-
cle, while the other boom reverses after a fixed delay.
If the MASTER barrier is completely open or completely closed and the SLAVE barrier is in an intermediate
position, the MASTER barrier sends a re-alignment command to the SLAVE barrier, with a 5 second pre-
manoeuvre flashing warning signal.
Conversely, if the MASTER barrier is in an intermediate position, after 5 seconds of pre-flashing it re-aligns
with the SLAVE barrier.
The alignment function is disabled if the "operator present" function
$
is enabled.
21(ST)
22(COM)
STOP command input (NC).
The current manoeuvre is arrested if the safety contact opens.
N.B.:
the controller is supplied with this contact already jumpered by ROGER TECHNOLOGY.
In the case of installations with two opposed barriers, if the STOP command signal is given for the
MASTER barrier, both barriers stop. If the STOP command signal is given for the SLAVE barrier, only the
SLAVE barrier stops.
23(COS)
22(COM)
Input (NC or 8.2 kOhm) for connecting sensing edge
COS
.
Movement is reversed (open) if the sensing edge is activated during closure.
If the sensing edge is not installed, jumper the terminals
23(COS)-22(COM)
or
set parameter
.
In the case of installations with two opposed barriers, the sensing edge (if installed) must be connected
to and configured for both the MASTER barrier and the SLAVE barrier.
24(FT)
13(COM)
Input (NC) for connecting photocell
FT
(fig. 4-5-6).
The photocells are configured by default with the following settings:
–
. Photocell triggers only during barrier closure. Photocell is ignored during barrier opening
manoeuvre.
–
. Movement is reversed if the photocell is triggered during barrier closure.
–
. The barrier opens when an open command is received if the photocell FT is obstructed.
If the photocells are not installed, jumper the terminals
24(FT)
-
25(COM)
or set the parameters
and
.
WARNING
! Use
G90/F4ES
or
T90/F4S
photocells.
In the case of installations with two opposed barriers, the photocells must be connected to and configured
for the MASTER barrier only.
In the case of installations with parking mode, the input
FT
may be used to receive a closing command
from a magnetic loop (NC) (see chapter 14).
27
26(ANT)
Antenna connector for slot-in radio receiver board.
Use RG58 if an external antenna is used - maximum recommended length: 10 m.
N.B.
: do not make joints in cable.
29(PED)
28(COM)
Partial open command input (NO).
The barrier is always opened completely when the contact is closed.
In the case of installations with two opposed barriers, the command PED only opens the MASTER barrier
when both barriers are completely closed.
In the case of installations with "Directional" parking mode (parameter
or
), the input PED
may be used to receive a closing command from a magnetic loop (NC) (see chapter 14).
29(PED) 28(COM)
The command input (N.C.) available for the connection of the sensor of the
ACS/BA/60
detachable
barrier boom coupling system (fig. 8)
When the
ACS/BA/60
detachable boom safety system intervenes, the contact switches from N.C. to N.O.
Enable the contact via parameter
.
30(PP)
28(COM)
Step mode command input (NO).
The function of this command is determined by parameter
$
.
30(PP) 28(COM)
The command input (N.C.) available for the connection of the sensor of the
ACS/BA/60
detachable
barrier boom coupling system (fig. 8)
When the
ACS/BA/60
detachable boom safety system intervenes, the contact switches from N.C. to N.O.
Enable the contact via parameter
.
31(CH)
28(COM)
Close command input (NO).
31(CH) 28(COM)
The command input (N.C.) available for the connection of the sensor of the
ACS/BA/60
detachable
barrier boom coupling system (fig. 8)
When the
ACS/BA/60
detachable boom safety system intervenes, the contact switches from N.C. to N.O.
Enable the contact via parameter
.
32(AP)
28(COM)
Open command input (NO).
Содержание CTRL
Страница 2: ...2 ...
Страница 16: ...16 13 ENC2 ENC1 LOCKS LED LIGHT ST COM 21 22 ENC2 ENC2 6 FILI 6 WIRES ENC1 7 FILI 7 WIRES ENC1 BIONIK4 ...
Страница 19: ...19 AGILIK KB MESSA A TERRA GROUNDING SCHEME 16 ...
Страница 20: ...20 17 MESSA A TERRA GROUNDING SCHEME BIONIK4 BIONIK4HP BIONIK6 BIONIK8 ...
Страница 290: ...290 ...
Страница 291: ...291 ...