Roger Technology Swing Gate Brushless B70-2DCHP Control Panel 

Quick Start Guide Extended Mode 

 

 

 

 

Step 7) THE STROKE PROGRAMMING SEQUENCE (also detailed in the main B70/2DCHP manual) 

WARNING! Before proceeding, make sure that: 

The doors are in a fully closed position: bring the doors into position by giving a close command, (CH) or with above 

ground motors by using the manual un-lock) so that they come right against the mechanical stop. Pay attention to 

the position of the lever arm of the BR21 underground motors: it must be properly hooked onto the door. To 

facilitate the operation, it is recommended to power off and then restart, so that you can give the close command 

regardless of the position of the door: the motor stops automatically when it reaches the mechanical closure stop. 

For the program starting from the fully closed position is important because the control unit performs a mapping of 

the absorption of current along the entire movement, while opening and then closing. For this reason, if a different 

path is detected between opening and closing the program fails and returns an error message of AP PL 

 

If the limit switches are present and connected, the motion stops when they are activated, otherwise the motors will 

stop on the motor adjustable stops or the gate wing stops set. 

 

If you change the value of par. 31 and/or 32 in extended mode it is necessary to repeat the programming. 

 

 

To enter programming press the PROG button for 4 s

.: the display will show 

AP P-

 ; at this point, you can 

programme the stroke by pressing the 

PROG button

 again, or by pressing 

the radio control

 button enabled by the 

step-by-step function. 

 

The display shows the indication 

AUTO

 and motor 1 starts opening, after the phase shift time. 

 

Programming is performed automatically.  Wait for the completion of the cycles avoiding crossing the ray of the 

photocells or activating other safety devices (safety edges, stop). 

The display shows the indication AU TO and motor 1 starts opening, after the phase shift time established in par. 25, 

motor 2 is also automatically activated; when the wings both reach the fully open position, stopping on the 

mechanical gate stop (or on the limit switch in the case of a motor with an articulated arm) the writing AU TO flashes 

on the display for 2 seconds indicating that it is going to close, then the indication AU TO stops flashing and the 

closing operation starts. If the program is successfully finished, the display goes back to showing the control and 

safety status. 

Otherwise, APPE appears (acquisition error) or APPL (path length error) and the program will have to be repeated. 

 

Restoring standard factory parameters.

 

Turn off the control unit, simultaneously press and hold the UP and DOWN buttons then turn on again while keeping 

the buttons pressed.  After 4 seconds the display will show the writing 

rE S-

 flashing, which indicates that the values 

have been restored to factory.  N.B.: parameter A1 in extended mode is not restored and should be checked again as 

well as the number of motors connected at 70 

 

 

 

 

Содержание B70-2DCHP

Страница 1: ...cables XYZ and earth to the XYZ points inside the control panel for each motor respecting that brushless motors need a minimum of 2 5mm cross section cable size If the cables to be connected to the motor are extended over 10 metres in total length a 4 0mm cross section cable must be used In the case on just 1 motor connect to Step 3 Connect the power supply to the control panel Press the test butt...

Страница 2: ...rossed on opposite sides so that you do not have two receivers at the same side The set on the gate posts 3 are on the outside of the gates For this purpose 5 core BT type cable is recommended for use CW1128 with conduit Follow the wiring diagram provided to wire both the receiver and transmitting photocells At the control box end wire the colour coded cables up as per the diagram provided showing...

Страница 3: ... positions of the collars by swinging the gate open closed with the motor unlocked Step Step 6 You should now be ready to carry out the stroke programming sequence But first you should check that the motors are traveling in the correct direction in relation to the control panel To do this it will be necessary to give the panel a brief open or close command and compare the command to the movement o...

Страница 4: ...ogramming press the PROG button for 4 s the display will show AP P at this point you can programme the stroke by pressing the PROG button again or by pressing the radio control button enabled by the step by step function The display shows the indication AUTO and motor 1 starts opening after the phase shift time Programming is performed automatically Wait for the completion of the cycles avoiding c...

Страница 5: ...red codes NOTE it s recommended to delete all codes at the first installation before starting storing codes Step 9 Test the system You can now test run the system with the fob If necessary reduce the impact force level with the menus 30 to 33 in the parameters These settings are explained in the manufacturers B70 2DCHP manual Step 10 Add in the necessary safety photocells safety edges and other de...

Страница 6: ...e 6 Connecting gate release devices Volt free release connections only The communication part of the intercom must use its own power supply Check that powered your devices will accept 24VDC Connection of the inductive loop detector PD132 230VAC for use as an exit device All dips off Road Loop ...

Страница 7: ...nology Swing Gate Brushless B70 2DCHP Control Panel Quick Start Guide Extended Mode 7 Connecting magnetic locks Connecting a 12V time clock GL Series Mag locks wiring detail N C White COM Green Not normally used ...

Страница 8: ...r safety if necessary integrating those in the manual for installation of the door gate and give the user a copy Compile the proof book and give the user a copy see facsimile in Annex 1 Draft the EC declaration of conformity see facsimile in Annex 2 and give the user a copy Fill in the label or plate with CE marking and attach it to the motorised door gate N B The technical file must be held and m...

Страница 9: ...E MACHINERY DIRECTIVE 98 37 EEC AND THE STANDARDS EN 13241 1 EN 12453 EN 12445 The risks listed below follow the sequence of the installation process These risks are those which are commonly present in motorised doors gates systems According to the various situations consideration therefore has to be made of any possible additional risks and exclude those which are not applicable The solutions to ...

Страница 10: ... force should be measured one leaf at a time Check that the values measured by the instrument are below those indicated in the graph Carry out the measurements in the following points L 50 300 and 500 mm H 50 mm at mid height of the leaf and at the height of the leaf minus 300 mm max 2500 N B The measurement should be repeated three times in each point and the average value considered The graph in...

Страница 11: ...tective device in accordance with the standard EN 12978 for example a sensitive edge and repeat the measurement 5 Impact in the area of closure Figure 1 risk C F Install a pair of photocells recommended height 500 mm so as to sense the presence of the test parallelepiped height 700 mm positioned as illustrated N B The test specimen for presence sensing is a parallelepiped 700 x 300 x 200 mm with 3...

Страница 12: ... Use CE marked components and materials pursuant to the Low Voltage Directive 73 23 EEC F Carry out the electrical connections connection to the mains earth connections and relevant checks in accordance with current regulations and as indicated in the installation manual of the drive unit N B If the electrical supply line is already set up via both a socket and a connector block declarations of co...

Страница 13: ...safety devices installed 1 7 1 1 7 2 1 7 3 1 7 4 1 6 1 1 1 2 Integration principles for safety and information 20 Signalling equipment 21 Warnings 22 Marking 23 Operating instructions 23 Maintenance 24 Unprotected residual risks F A flashing light should be installed in a visible position to indicate movement of the leaf F Traffic lights can be installed to control vehicle traffic F Reflectors can...

Отзывы: