background image

 

 

 

The Constant Fraction Discriminators CFD8c, CFD7x, CFD4c, CFD1c and CFD1x (11.0.1701.1) 

Page 11 of 25  

: Rule for Delay 

   

 

Figure 3.8b: Signal traces similar as in Figure 3.7b for poorly adjusted 

Threshold level:

 analogue monitor output, 

digital monitor output (only in left picture) and CFD output. Left picture: for too high threshold settings only input 

signals with very high amplitudes are registered. When setting the correct Threshold level, the dark area shown by 

the arrow would be filled with smaller amplitude signals. Right picture: threshold setting too low (i.e. in the noise) 

Sometimes it is necessary to compromise and allow a certain amount of noise triggers in situations where the noise level is not 

well separated from the signals. This is acceptable if the random signals do not affect the measurement and their rate does not 

exhaust the data acquisition capability of circuits in follow-up electronics (e.g. a TDC or TAC). If the threshold is set too high, 

signals are lost. 

3b.3.2

 

CFD delay 

The 

CFD delay

 must correspond to the input signal rise time and is set by bridging the “Delay”-sockets with an appropriate 

cable (LEMO 00 series). As a thumb rule, a 1m long coax cable will produce an external delay of 5 ns. It is to note that the 

RoentDek

 

CFDs have an additional internal offset delay of about 0.5 ns. A 1 m (5 ns) external delay cable thus results in a 

total delay D of 5.5 ns. Note, that the 

RoentDek

 

CFDs will not operate without connecting an external delay cable bridge. 

 

If the pulse rise time RT is defined as the time from reaching 10% to 90% of the signal maximum, the delay shall be equal or 

smaller (50-80%) than this rise time RT, depending on the 

CFD fraction

 ratio f. For small 

CFD fractions

 (< 0.5) a thumb rule for 

an appropriate delay D is  

 

D = RT (1-f) 

 

However, a delay D < ½ RT is not recommended even for CFD fractions higher than 0.5. 

 

If a 

RoentDek

 

CFD is delivered as part of a detector system, appropriate cables are usually included. Cables with 1-3 ns 

delay shall be used for the MCP timing signal and cables with 4 or 5 ns delay are recommended for the delay-line signals (10 ns 

in case of LC-delay-line anodes). Sometimes, especially for large-size detectors it may be of advantage to use longer delay 

cables. 

 

The input pulses in Figure 3.7b have about 6 ns rise time, the chosen cable delay results in a CFD delay of 4.5 ns, which is 

close enough to the optimal value of 4 ns for the selected CFD fraction of 0.35. If the delay cable is too long, the two 

intermediate signals (inverted/delayed, respectively) do not merge into a “proper” bipolar signal (see Figure 3.9b left). If the 

delay cable is too short, no distinct cross over is formed from the intermediate signals (see Figure 3.9b right). The CFD cannot 

function properly under any such 

CFD delay

  settings. A non-perfect choice of delay can sometimes be compensated by 

adjusting the 

CFD fraction

 (see below) as long as D/RT is between 0.5 and 1 (see Figure 3.10b)

Equation 3.1b  

Содержание CFD1c

Страница 1: ...Dek Handels GmbH Supersonic Gas Jets Detection Techniques Data Acquisition Systems Multifragment Imaging Systems The RoentDek Constant Fraction Discriminators CFD8c CFD7x CFD4c CFD1c and CFD1x 11 0 17...

Страница 2: ...Kernphysik Max von Laue Str 1 D 60438 Frankfurt am Main Germany Web Site www roentdek com WEEE DE48573152 Product names used in this publication are for identification purposes only and may be tradema...

Страница 3: ...3 CFD fraction 12 3b 3 4 Walk level 13 3b 3 5 Output signal width 14 3B 4 THE VETO OPTION 14 3b 4 1 Accessing the jumpers in CFD1c CFD1x 16 3b 4 2 Accessing the jumpers in CFD8c and CFD7x 16 3b 4 3 A...

Страница 4: ...Page 4 of 25 The Constant Fraction Discriminators CFD8c CFD7x CFD4c CFD1c and CFD1x 11 0 1701 1...

Страница 5: ...Constant Fraction DiscriminatorsCFD8b CFD4b and CFD1b 11 0 1701 1 Page 5 of 25...

Страница 6: ...odules containing such boards please review first Chapters 3b 1 to 3b 3 and then refer to Chapter 3b 7 to learn about the difference between the standard CFD and the RoentDek bCFD settings 3b 1 Genera...

Страница 7: ...weight 0 8 kg with an external 12 V DC mains adapter for use with 100 250 V AC sockets The power consumption is max 0 5 A at 12 V DC 6 W or max 0 7 A at 12 V DC 10 W for the CFD1x The CFD4c has the s...

Страница 8: ...fraction is determined by the choice of fix resistors or a potentiometer as in case of the RoentDek CFDs While one of the signals is inverted later on the other experiences a certain delay CFD delay...

Страница 9: ...he signals have to be verified on an oscilloscope The CFD Fraction can be adjusted by another potentiometer labelled Fr on the front panel CFD4b CFD1b side panel CFD8b top lid see Figure 3 6b Figure 3...

Страница 10: ...s damped by a factor of 10 For achieving the ideal settings it is first of all important to note that the CFD operates best in all respects and yields the optimal temporal resolution if the input sign...

Страница 11: ...delay D of 5 5 ns Note that the RoentDek CFDs will not operate without connecting an external delay cable bridge If the pulse rise time RT is defined as the time from reaching 10 to 90 of the signal m...

Страница 12: ...livers the CFD with a standard CFD fraction setting of about 0 35 The CFD fraction can be varied between 0 15 and 1 via a potentiometer In order to observe and quantify the CFD fraction ratio on the o...

Страница 13: ...during the bipolar signal s crossover while fluctuating almost equally between high and low states before and long after the signal due to electronic noise on the line not visible in the pictures If...

Страница 14: ...idth bridges of the internal circuit see Figure 3 5b With the jumper in place the maximum width is increased to 2000 ns Please contact RoentDek if you are in need of the optional jumpers Obviously a s...

Страница 15: ...15b Trace of the input signal to the Veto socket upper trace and signal traces of CFD timing signals lower trace integrated over many events for Veto left and Gating mode right In order to work reliab...

Страница 16: ...he front panel 3b 4 2 Accessing the jumpers in CFD8c and CFD7x I Disconnect the mains power supply II On the rear panel remove all five screws red circles Please note that different types and sizes of...

Страница 17: ...ear front panel and fix them with all screws and hex bolts 3b 4 3 Accessing the jumpers in CFD4c I Remove all six screws from the right side panel marked in red see Figure 3 20b Figure 3 20b Side pane...

Страница 18: ...oscope see Figure 3 21b If a CFD is used for operating a RoentDek delay line detector or similar device these pre trigger events result in a distinct structure in the time sum spectrum see Figure 3 21...

Страница 19: ...neighbours 3b 6 The CFDx pulse height determination option The CFDx function is an add on circuit that allows measuring the signal s pulse height The pulse height information is coded as a time delay...

Страница 20: ...er trace ramp monitor output the Ramp switch is turned off here Signals are triggered on the CFD timing output signal trace not shown Left and right pictures were obtained with two different cable len...

Страница 21: ...Dx signal This is indicated in Figure 3 26b The ramp slope is about 1 V per 12 ns giving an almost linear correspondence between pulse height and time delay with a typically 10 to 20 ns offset for pul...

Страница 22: ...iming signal with a RoentDek TDC8HP The same spectrum could be recorded by plotting the time difference between trailing and leading transitions of the CFDx output It is advisable to mark the pulse he...

Страница 23: ...se heights will not be registered Please contact RoentDek for advice unless you have received a properly matched system with bFAMP for a certain delay line read out anode Timing signals off the MCP co...

Страница 24: ...3 12B SIGNAL TRACES AS IN FIGURE 3 8B LEFT WITH THE WALK LEVEL SET TO THE BASELINE OF THE INPUT SIGNALS LEFT PICTURE AND SLIGHTLY TOWARDS THE POSITIVE SIDE WHERE THE NOISE TRIGGERS BEGIN TO VANISH RIG...

Страница 25: ...DTH POTENTIOMETER SETTING LOWER TRACE RAMP MONITOR ALL TRACES TRIGGERED ON THE STOP SIGNAL THE STOP SIGNAL SHOULD BE USED IF THERE IS A SPARE TDC CHANNEL AVAILABLE 21 FIGURE 3 27B AS FIGURE 3 25B RIGH...

Отзывы: