Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021
35
Chapter 6
Fault Finding and Maintenance
Output Module faults are reported to the user through visual indicators on
the Front Panel of the Module and through status variables, which may be
automatically monitored in the application programs and external system
communications interfaces. There are generally two types of faults that must
be remedied by the user: external wiring and Module faults. External wiring
faults require corrective action in the field to repair the fault condition.
Module faults require replacement of the Output Module.
By measuring the output channel voltage and current, the Module
automatically detects field-wiring and load faults. When a field signal fails
open circuit, short circuit or there is no field supply voltage connected, the
output status indicator displays the configured LED mode, the corresponding
output state is reported and the line fault status for that channel is set to ‘1’. All
other output channels are unaffected, except in the case of common cause
wiring and supply voltage faults in the field.
The field output voltage and current variables can be monitored to determine
the actual operating conditions of each output channel. This additional
information assists the user in determining the specific type of wiring fault.
Once the specific field-wiring fault has been identified and corrected, the
output status variables and output status indicator display the normal on/off
status of the field device.
Extensive diagnostics provide the automatic detection of Module faults. The
TMR architecture of the Output Module and the diagnostics performed verify
the validity of all critical circuits. Using the TMR architecture provides a Fault
Tolerant method to withstand the first fault occurrence on the Module and
continue normal output controls without interruption in the system or
process. Faults are reported to the user through the Healthy status indicators
on the Front Panel of the Module and through the INFO and HKEEPING
variables. Under normal operations, all three Healthy Indicators are green.
When a fault occurs, one of the Healthy Indicators is flashing red. It is
recommended that this condition is investigated and if the fault is within the
Module, it should be replaced.
Module replacement activities depend on the type of spare Module
configuration that is chosen when the system was configured and installed.
The Module may be configured with a Dedicated Standby Slot or with a
SmartSlot for a spare replacement Module.
Fault Reporting
Field Wiring Faults
Module Faults