Chapter 4
Application
28
Rockwell Automation Publication ICSTT-RM451D-EN-P - March 2021
Channel
Description
FCR
Units (Full Scale Range)
50
B
51
C
52
A
FIU Board Temperature, Output Group 5
(Note: Temperature, °C = input value / 256)
-32768
32767
-
53
B
54
C
55
A
Diagnostic error code
56
B
57
C
Each input within the housekeeping rack is reported as an integer. In general,
the application engineer does not normally require these inputs. They are
provided to aid fault finding and diagnosis and may be used for reporting and
display purposes. If a slice is Fatal, then all reported housekeeping inputs are
set to zero.
Rack 8: INFO
This table describes Rack 8: INFO:
Table 13 Rack 8: INFO Descriptions
Channel
Description
1
Active Module chassis number
2
Active Module slot number
3
Active Module healthy
4
Active Module mode
5
Standby Module chassis number
6
Standby Module slot number
7
Standby Module healthy
8
Standby Module mode
9
FCR status
10
Primary Module is active
11
Active Module is simulated
The Active Module chassis and slot numbers indicate the position of the
currently Active Module. These values change to match the primary or
secondary Module position, depending on their Active status, that is,
Active/Standby changeover “swaps” the values for the Active Module chassis
and slot number channels with those in the Standby Module chassis and slot
number channels. The chassis and slot numbers are set to zero if the Module
is not present.
The Active and Standby Module healthy channel is returned as an integer,
however only the least significant bit is used. A value of 0 indicates that a fault
has been detected, a nonzero value indicates that the Module is healthy.
The Active and Standby Module Mode is an integer indicating the current
operating mode of the associated Module. The value indicates the current
internal operating mode of the Module.