Programming
4-9
Dual Ramp Start
The SMC-Flex controller provides the user with the ability to select
between two Start settings. The parameters below are available in the
Set Up programming mode. To obtain Dual Ramp control, Ramp #1
is located in the Basic Set Up and Ramp #2 is located in the Option 2
Input (Dual Ramp).
➀
The Dual Ramp feaure is available on the standard controller.
➁
Kickstart can be programmed for both start modes.
Parameter
Option
Set Up
The user must select the Set Up programming mode to obtain
access to the Dual Ramp parameters.
—
Basic Set Up/Starting Mode
Set Up as stated in previous pages.
—
Option 2 Input (Dual Ramp)
➀
This allows the user the option to choose between two Soft Start
profiles defined by:
1. Start Mode/Ramp Time/Initial Torque and
2. Start Mode 2/Ramp Time 2/Initial Torque 2.
When this feature is turned on, the ramp time/initial torque
combination is determined by a hard contact input to terminal 15.
When this input signal is low, ramp time/initial torque are selected.
When this input is high, ramp time 2/initial torque 2 are selected.
Once the Option 2 Input has been set to Dual Ramp, you must ESC
back to the Parameter (File) menu. Re-enter into the Set Up menu to
show both Basic Set Up and Dual Ramp.
—
Basic Set Up/Start Mode
➁
This selects the start mode for option #1.
—
Basic Set Up/Ramp Time
This programs the time period during which the controller will ramp
the output voltage up to full voltage for the first Start setup.
0…30 s
Basic Set Up/Initial Torque
This parameter establishes and adjusts the initial reduced output
voltage level for the first Soft Start setup.
0…90%
locked rotor
torque
Dual Ramp/Start Mode 2
➁
This selects the start mode for option #2.
—
Dual Ramp/Ramp Time 2
This programs the time period during which the controller will ramp
the output voltage up to full voltage for the second Start setup.
0…30 s
Dual Ramp/Initial Torque 2
The initial reduced output voltage level for the second Start setup is
established and adjusted with this parameter.
0…90%
locked rotor
torque
Содержание SMC-Flex
Страница 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Страница 4: ...Notes...
Страница 30: ...1 22 Product Overview Notes...
Страница 126: ...9 8 Troubleshooting...
Страница 148: ...B 14 Parameter Information Notes...
Страница 150: ...C 2 Renewal Parts Notes...
Страница 152: ...D 2 Contactor Replacement Installation Instructions for 625 1250 A units 1 2 Step B Step C 1 2 3 1...
Страница 153: ...Contactor Replacement Installation Instructions for 625 1250 A units D 3 1 3 4 2 E I E E I E Step D Click...
Страница 156: ...E 2 Accessories Notes...