Product Overview
1-3
Selectable Kickstart
This feature provides a boost at startup to break away loads that
require a pulse of high torque to get started. This is intended to
provide a pulse of current that is selectable from 0…90% of locked
rotor torque. Selectable kickstart is user-adjustable from
0.0…2.0 seconds.
Figure 1.2 Selectable Kickstart
Current Limit Start
➀
This starting mode provides a true current limit start; it is used when
limiting maximum starting current is necessary. The Current Limit
level is user-adjustable from 50…600% of the motor full load ampere
rating; and the current limit time is user-adjustable from 0…30
seconds. If the SMC-Flex controller senses that the motor has reached
the up-to-speed condition during the current limit starting mode, the
internal bypass contactor will be pulled in.
Figure 1.3 Current Limit Start
➀
Kickstart is also available with Current Limit Start.
Start
Run
100%
Initial
Torque
Percent
Voltage
Time (seconds)
Selectable Kickstart
Soft Stop
Coast-to-rest
Soft Stop
Start
600%
50%
Percent Full
Load Current
Time (seconds)
Содержание SMC-Flex
Страница 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Страница 4: ...Notes...
Страница 30: ...1 22 Product Overview Notes...
Страница 126: ...9 8 Troubleshooting...
Страница 148: ...B 14 Parameter Information Notes...
Страница 150: ...C 2 Renewal Parts Notes...
Страница 152: ...D 2 Contactor Replacement Installation Instructions for 625 1250 A units 1 2 Step B Step C 1 2 3 1...
Страница 153: ...Contactor Replacement Installation Instructions for 625 1250 A units D 3 1 3 4 2 E I E E I E Step D Click...
Страница 156: ...E 2 Accessories Notes...