Chapter
9
Troubleshooting
Introduction
For safety of maintenance personnel as well as others who might be
exposed to electrical hazards associated with maintenance activities,
follow the local safety related work practices (for example, the NFPA
70E, Part II in the United States). Maintenance personnel must be
trained in the safety practices, procedures, and requirements that
pertain to their respective job assignments.
Note: The time it takes for the motor to come up to speed may be
more or less than the time programmed, depending on the
frictional and inertial characteristics of the connected load.
Note: Depending on the application, the Braking options (SMB
Motor Braking, Accu-Stop, and Slow Speed) may cause
some vibration or noise during the stopping cycle. This may
be minimized by lowering the braking current adjustment. If
this is a concern in your application, please consult the
factory before implementing these options.
ATTENTION
!
Hazardous voltage is present in the motor circuit
even when the SMC-Flex controller is off. To avoid
shock hazard, disconnect main power before
working on the controller, motor, and control
devices such as Start-Stop push buttons. Procedures
that require parts of the equipment to be energized
during troubleshooting, testing, etc., must be
performed by properly qualified personnel, using
appropriate local safety work practices and
precautionary measures.
ATTENTION
!
Disconnect the controller from the motor before
measuring insulation resistance (IR) of the motor
windings. Voltages used for insulation resistance
testing can cause SCR failure. Do not make any
measurements on the controller with an IR tester
(megger).
Содержание SMC-Flex
Страница 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Страница 4: ...Notes...
Страница 30: ...1 22 Product Overview Notes...
Страница 126: ...9 8 Troubleshooting...
Страница 148: ...B 14 Parameter Information Notes...
Страница 150: ...C 2 Renewal Parts Notes...
Страница 152: ...D 2 Contactor Replacement Installation Instructions for 625 1250 A units 1 2 Step B Step C 1 2 3 1...
Страница 153: ...Contactor Replacement Installation Instructions for 625 1250 A units D 3 1 3 4 2 E I E E I E Step D Click...
Страница 156: ...E 2 Accessories Notes...