A-2
Specifications
Electrical Ratings
➀
690V power is only available with 100…240V control
.
Device Rating
UL/CSA/NEMA
IEC
Power Circuit
Rated Operation Voltage
480V
200…480V AC
(–15%, +10%)
200…415V
600V
200…600V AC
(–15%, +10%)
200…500V
690V
230…600V AC
(–15%, +10%)
230…690V/Y
(–15%, +10%)
Rated Insulation Voltage
480V
N/A
500V
600V
500V
690V
690V
Rated Impulse Voltage
480V
N/A
6000V
600V
690V
Dielectric Withstand
480V
2200V AC
2500V
600V
690V
Repetitive Peak Inverse
Voltage Rating
480V
1400V
600V
1600V
690V
1800V
Operating Frequency
All
47…63 Hz
Utilization Category
5…480 A
MG 1
AC-53B: 3.0-50:1750
625…1250 A
MG 1
AC-53B: 3.0-50:3550
Protection Against Electrical
Shock
5…85 A
N/A
IP20
108…480 A
IP2X (with terminal
covers)
625…1250 A
IP00 (open Device)
DV/DT Protection
480V & 600V
RC Snubber Network
690V
None
Transient Protection
480V & 600V
Metal Oxide Varistors: 220 Joules
690V
None
Control Circuit
Rated Operation Voltage
➀
5…480 A
100…240V AC or 24V AC/DC
625…1250 A
110/120V AC and 230/240V AC
Rated Insulation Voltage
All
N/A
240V
Rated Impulse Voltage
All
N/A
3000V
Dielectric Withstand
All
1600V AC
2000V
Operating Frequency
All
47…63 Hz
Input on-state voltage minimum
85V AC, 19.2V DC / 20.4V AC
Input on-state current
20 mA @120V AC/
40 mA @ 240V AC, 7.6 mA @ 24V AC/DC
Input off-state voltage maximum
50V AC, 10V DC / 12V AC
Input off-state current @ input off-state
voltage
<10 mA AC, <3 mA DC
Содержание SMC-Flex
Страница 1: ...USER MANUAL FOR SERIES B SMC Flex BULLETIN 150...
Страница 4: ...Notes...
Страница 30: ...1 22 Product Overview Notes...
Страница 126: ...9 8 Troubleshooting...
Страница 148: ...B 14 Parameter Information Notes...
Страница 150: ...C 2 Renewal Parts Notes...
Страница 152: ...D 2 Contactor Replacement Installation Instructions for 625 1250 A units 1 2 Step B Step C 1 2 3 1...
Страница 153: ...Contactor Replacement Installation Instructions for 625 1250 A units D 3 1 3 4 2 E I E E I E Step D Click...
Страница 156: ...E 2 Accessories Notes...