Installation
Node Controller Installation
Node Controller Hardware User Manual
93
Rockwell Automation Publication MMI-UM013B-EN-P - April 2020
3.
Install cable management as required to secure the cables that are connected to the
node controller.
Rack Mounting
The NC-12 can be mounted in a standard 19 inch rack by attaching the optional 2Urack
mounting brackets as shown in
. See
Figure 5-7: NC-12 Node Controller Rack Mounting
1.
Remove the two M5 x 10 mm screws from the front of each side (four screws total).
2.
Align each rack mounting bracket to the NC-12 and secure them to the node controller
with two M5 X 12 mm flat head screws. Tighten to 2.0 N•m [18 in•lb] (four screws
total).
3.
Locate the node controller in the rack and secure it with four screws (two per mount-
ing bracket) as specified by the rack manufacturer. Make sure that the service and
exclusion zones are maintained.
4.
Install cable management as required to secure the cables that are connected to the
node controller.
M5 Screw
(4X)
Mounting Bracket
(2X)
M5 x 10 mm
(4X)
Содержание MagneMotion 700-0871-00