Rockwell Automation Publication 280E-PM001A-EN-P – August 2011
89
ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
Chapter
C
b. Click
Apply
, the following screen should pop-up. Click
Yes
. Then click
OK
to close out the AOP.
c. You should see the yellow inhibit symbol next to the ArmorStart in the
I/O Configuration tree showing that the module is inhibited.
10.
Execute the instruction by toggling the
Reset
input that was created
earlier.
a. Energize the bit by left mouse clicking on the input and pushing
CTRL+T
. De-energize the bit with
CTRL+T
again.
b. You should see the status LEDs on the ArmorStart display the
Reset
and
Power Cycle
sequence. You should also see the
Done (DN)
bit of
the message turn green indicating that the reset was successful.
11.
Verify the reset worked by bringing the ArmorStart's web browser back up
and verifying that the
User Name
is
Administrator
and that there is no set
password.
12.
Uninhibit the ArmorStart module through the AOP and plug any I/O
connections back into the ArmorStart.