Rockwell Automation Publication 280E-PM001A-EN-P – August 2011
75
ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
Appendix
A
Table 7 - "Steady Red" MOD LED Status
(Refer to Table 6 above.)
Fault Type
Description
0
EEPROM Fault
Non-volatile memory value out of range for a local parameter, or a write failure detected. This fault
is also reflected by a solid red MOD status LED.
1
Internal Comm2
The Internal communication connection has timed out. This fault is also reflected by a flashing red
MOD status LED.
2
Hardware Fault
Internal diagnostics checks failed. This fault is also reflected by a solid red MOD status LED.
3
Control Module An illegal or unsupported Control Module product code or revision has been detected. Also reported
if no Control Module is detected on power up. This fault is also reflected by a solid red MOD status
LED.
4…15
Reserved
Reserved
Table 8 - Network LED Status Indication
NET Status LED
Description
Recommended Action
Flashes
Green-Red-Off
The device has not completed the initialization, is
not on an active network, or may not be powered up.
Check to make sure the product is properly wired
and configured on the network.
Solid Green
The device is operating in a normal condition.
No action required.
Flashing Green
The device is operating in a normal condition.
No action required.
Flashing Red
Internal network fault has occurred.
Check 3-phase and control power connections.
Check ethernet connections.
Solid Red
The device has detected a major error that has
rendered it incapable of working.
Troubleshooting should be done to ensure that
the control module internal switch settings are
correct. Consult factory.