18
Rockwell Automation Publication 280E-PM001A-EN-P – August 2011
Chapter 2
ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
Parameters Tab
Return to the Parameters tab again once the AOP is opened by selecting the
ArmorStart in the project tree. Notice that when clicking in the Parameters tab,
an
ArmorStart Correlation
pop-up window is displayed, as shown below.
This indicates that the AOP is comparing the parameter data entered offline vs.
the parameter data stored in the ArmorStart. If any discrepancies are found
between the parameters in the AOP and the parameters in the ArmorStart, a
window will pop-up, as shown below, asking you to decide which parameters you
want to keep.
If you want to keep the parameters in the AOP, select
Download
. If you want to
keep the parameters in the ArmorStart, select
Upload
. Otherwise, select
Cancel
.
Clicking
Cancel
will lock the user out of viewing the values. If you are connected