78
Rockwell Automation Publication 280E-PM001A-EN-P – August 2011
Appendix B
ArmorStart
®
EtherNet/IP
™
Communications & Control Programming Manual
1.
Remove the protective caps from the rotary switches.
2.
Set the Network IP address by adjusting the three switches on the front of
the I/O module using a flat head screwdriver
3.
Set up the switches in a range from 001 to 254. In this example we are
setting them to 163.
When the switches are set to a valid number, the adapter's IP address will
be 192.168.1.xxx (where xxx represents the number set on the switches). In
this example the IP address is 192.168.1.163. The adapter's subnet mask
will be 255.255.255.0 and the gateway address is set to 0.0.0.0. A power
cycle is required for any new IP address to take effect.
Note:
The user cannot change the IP address from 192.168.1.xxx when
using the IP address switches. The top three octets are fixed. DHCP,
BootP, or the embedded web server must be used to configure the address
to a value different than 192.168.1.xxx. Also, the adapter will not have a
host name assigned, or use any Domain name System when using the
rotary switch settings.
4.
If the switches are set to an invalid value (such as 000 or value greater than
254), the adapter will check to see if the DHCP is enable. If so, the adapter
requests an address from a DHCP server. The DHCP server will also
assign other Transport Control Protocol (TCP) parameters. If DHCP is
not enabled, the adapter will use the IP address (along with other TCP
configurable parameters) stored in nonvolatile memory.
Protective IP67 Caps
Writable surface for IP address