Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
77
AFE in IP21 Rittal Enclosure – Installation/Wiring
Chapter 2
I/O Cable Grounding
When installing shielded multi-conductor cable for analog and digital I/O,
strip the cable from the terminal plug so you can fix it to the cable clamp for
grounding.
ATTENTION:
For the AFE in the IP21 Rittal enclosure, digital inputs 1, 3, 4,
and 5, and digital outputs 1 and 2, are wired at the factory and
programmed to operate from the controls on the front of the enclosure.
Digital output 3 is programmable and factory-wired for +24V DC only. Do
not change the wiring and programming for those digital inputs and
outputs, or it results in malfunction of the system.
Position the
exposed shield so
the clamp grips it.
IMPORTANT
: This clamp is not designed for strain relief.
Содержание Allen-Bradley PowerFlex 700AFE
Страница 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Страница 124: ...124 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 4 Programming and Parameters Notes ...
Страница 136: ...136 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 5 Troubleshooting Notes ...
Страница 158: ...158 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix A Supplemental Information Notes ...
Страница 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Страница 180: ...180 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index by number 120 linear list 120 viewing 163 ...
Страница 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Страница 185: ......