138
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Appendix A
Supplemental Information
Category
Specification
Protection
AFE Voltage Class
380/400V
480V
600V
690V
Bus overvoltage trip
911V DC
911V DC
1200V DC
1200V DC
Bus undervoltage shutoff/fault
333VDC
333V DC
461V DC
461V DC
Heat sink thermistor
Monitored by microprocessor overtemp trip
Ground fault protection
Yes
Input phase loss protection
Yes
Input overcurrent protection
Yes
Overtemperature protection
Yes
LCL filter overtemperature protection
Yes
Line transients
Up to 6000V peak per IEEE C62.41-1991
Control logic noise immunity
Showering arc transients up to 1500V peak
Ground fault trip
DC bus-to-ground current exceeds par 082 [Ground I Lvl] value
Environment
Altitude
1000 m (3300 ft) max. without derating
Max surrounding air temperature without
derating
0…40 °C (32…104 °F); Frame 13 600/690V AFE is rated at 35 °C
(95 °F). See
Derating Guidelines on page 139
(95 °F).
Storage temperature (all constructions)
–40…+60 °C (–40…+140 °F)
Atmosphere
Important:
The AFE unit
must
not
be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors, or dust.
If the AFE is not going to be installed for some time, store the AFE in an
area where it is not exposed to a corrosive atmosphere.
Relative humidity
5…95% noncondensing
Shock (non-operational)
15G peak for 11 ms duration
EN50178 / EN60068-2-27
Vibration
1 mm (0.039 in.) displacement, 1G peak
EN50178 / EN60068-2-6
Sound:
Frame 10
Frame 13
71 dB at 1 m (3.28 ft)
80 dB at 1 m (3.28 ft)
Electrical
AC input voltage tolerance
±10%
Frequency tolerance
48…63 Hz
Input phases
Three-phase input provides full rating for all AFEs. The AFE cannot be
operated with single-phase input.
Displacement power factor
1.0 default across entire range
Efficiency
97.5% at rated amps, nominal line volts
Short circuit rating:
• AFE Frame 10 in IP20
• AFE Frame 13 in IP20
• AFE in IP21 or AFE IP00
• 100 kA for 400/480V unit; 65 kA for 600/690V unit
• 100 kA for 400/480V unit; 100 kA for 600/690V unit
• Determined by AIC rating of installed fuse/circuit breaker
Control
AFE Voltage Class
380/400V
480V
600V
690V
DC output voltage range
462…702
583…842
700…932
802…1071
Method
Sine-coded PWM
Carrier frequency
3.6 kHz
Intermittent overload:
• Normal duty
• Heavy duty
• 110% overload capability for up to 1 minute
• 150% overload capability for up to 1 minute (this heavy-duty
rating does not apply to Frame 13 600/690V AFEs
Current limit capability
Current limit programmable from 20…150% of rated input current.
Содержание Allen-Bradley PowerFlex 700AFE
Страница 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Страница 124: ...124 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 4 Programming and Parameters Notes ...
Страница 136: ...136 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 5 Troubleshooting Notes ...
Страница 158: ...158 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix A Supplemental Information Notes ...
Страница 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Страница 180: ...180 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index by number 120 linear list 120 viewing 163 ...
Страница 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Страница 185: ......