Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
155
Supplemental Information
Appendix A
Logic Command Word for PowerFlex 750-Series Drives
Logic Bits
31 30 29
28 27 26 25 24 23
22 21 20 19 18 17
16 15 14 13 12 11
10 9
8
7
6
5
4
3
2
1
0
Command
Description
x
Normal Stop
0 = Not normal stop
1 = Normal stop
x
Start
(1)
0 = Not start
1 = Start
x
Jog 1
(2)
0 = Not jog 1 (Par. 556)
1 = Jog 1
x
Clear Fault
(3)
0 = Not clear fault
1 = Clear fault
x
x
Unipolar Direction
00 = No command
01 = Forward command
10 = Reverse command
11 = Hold direction control
x
Manual
0 = Not manual
1 = Manual
x
Reserved
x
x
Accel Time
00 = No command
01 = Use Accel Time 1 (Par. 535)
10 = Use Accel Time 2 (Par. 536)
11 = Use present time
x
x
Decel Time
00 = No command
01 = Use Decel Time 1 (Par. 537)
10 = Use Decel Time 2 (Par. 538)
11 = Use present time
x
Ref Select 1
000 = No command
001 = Ref A Select (Par. 545)
010 = Ref B Select (Par. 550)
011 = Preset 3 (Par. 573)
100 = Preset 4 (Par. 574)
101 = Preset 5 (Par. 575)
110 = Preset 6 (Par. 576)
111 = Preset 7 (Par. 577)
x
Ref Select 2
x
Ref Select 3
x
Reserved
x
Coast Stop
0 = Not coast to stop
1 = Coast to stop
x
Current Limit Stop
0 = Not current limit stop
1 = Current limit stop
x
Run
(4)
0 = Not run
1 = Run
x
Jog 2
0 = Not Jog 2 (Par. 557)
1 = Jog 2
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
x
Reserved
(1)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition starts the drive.
(2)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog 1/Jog 2 condition jogs the drive. A transition to a ‘0’ stops the drive.
(3)
To perform this command, the value must switch from ‘0’ to ‘1’.
(4)
A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Run condition runs the drive. A transition to a ‘0’ stops the drive.
Содержание Allen-Bradley PowerFlex 700AFE
Страница 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Страница 124: ...124 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 4 Programming and Parameters Notes ...
Страница 136: ...136 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 5 Troubleshooting Notes ...
Страница 158: ...158 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix A Supplemental Information Notes ...
Страница 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Страница 180: ...180 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index by number 120 linear list 120 viewing 163 ...
Страница 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Страница 185: ......