104
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 4
Programming and Parameters
DYNAMI
C C
ONTR
OL
P
arall
el
Mode
085
[Droop]
Sets the droop as % of active current reference for current balancing when AFEs are used in parallel
independent mode. It affects DC bus voltage if enabled. Recommended value for parallel AFEs is 5%.
Default:
Min/Max:
Units:
0.00%
0.00/100.00%
0.01%
086
[PWM Synch]
Sets synchronization to reduce the circulating current between parallel connected AFEs when they are
connected to the same DC bus and are fed from the same incoming power source without an isolation
transformer. In this case, parameter 085 [Droop] must be set to 5% in all AFEs, and this parameter 086
[PWM Synch] must be set to ‘1’ (Enabled).
Default:
Options:
0
0
1
Disabled
Disabled
Enabled
087
[Start Up Delay]
Sets a starting delay when Run command is given. When programming different delay to parallel
AFEs, the AFEs start in sequence.
Default:
Min/Max:
Units:
0.00 sec
0.00/300.00 sec
0.01 sec
Fil
e
Gr
oup
No.
Parameter Name and Description
Values
Содержание Allen-Bradley PowerFlex 700AFE
Страница 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Страница 124: ...124 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 4 Programming and Parameters Notes ...
Страница 136: ...136 Rockwell Automation Publication 20Y UM001F EN P April 2017 Chapter 5 Troubleshooting Notes ...
Страница 158: ...158 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix A Supplemental Information Notes ...
Страница 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Страница 180: ...180 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index by number 120 linear list 120 viewing 163 ...
Страница 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Страница 185: ......