Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020
315
Component Definition and Maintenance
Chapter 5
16.
Apply a 60Hz, 33% duty cycle signal to the OP1 fiber optic input.
17.
Verify that the diagnostics transmitter LED, OT1, is on.
18.
Verify that the signals at TP9 and TP8 are as shown in
.
19.
Verify that the signal between TP1 and TP2 is as shown in
.
20.
Remove the jumper between TB3-1 and TB3-2.
21.
Apply a constant fiber optic signal to the OP1 input.
22.
Apply a 60 Hz, 33% duty cycle signal, at a 0 to +2V level, between the
TB1-2 input and COM. Verify the signals in
there should be a 220 μS, ±20 μS time between the
rising edge of the U4-pin7 pulse and the falling edge of the TP7 signal.
Figure 261 - Gating pulses
Содержание Allen-Bradley PowerFlex 7000
Страница 32: ...32 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 1 Overview of Drive Notes ...
Страница 90: ...90 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 2 Drive Installation Notes ...
Страница 174: ...174 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 4 Commissioning NOTES ...
Страница 264: ...264 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 4 Commissioning Notes ...
Страница 412: ...412 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 5 Component Definition and Maintenance ...
Страница 420: ...420 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix A Catalog Number Explanation Notes ...
Страница 428: ...428 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix C Meggering Notes ...
Страница 432: ...432 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix D Preventative Maintenance Schedule Notes ...
Страница 433: ......