Rockwell Automation Publication 7000L-UM301F-EN-P - March 2020
301
Component Definition and Maintenance
Chapter 5
Figure 249 - Converter PowerCage Module (Service – per Step 6)
Loosen the hose clamp of the top hose of the outlet manifold of the chill
block to be serviced. Slide the hose clamp toward the chill block.
7.
Have a hose plug assembly and a M10 bolt ready. Per
, pull the
hose from the upper manifold hose barb and collect the fluid in a
container.
Figure 250 - Converter PowerCage Module (Service – per Step 7)
8.
Per
, insert the hose plug on the hose barb of the upper
manifold. Insert a M10 bolt in the end of the chill block hose. Note that
there may still be limited fluid leakage during this procedure.
Clamps
Содержание Allen-Bradley PowerFlex 7000
Страница 32: ...32 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 1 Overview of Drive Notes ...
Страница 90: ...90 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 2 Drive Installation Notes ...
Страница 174: ...174 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 4 Commissioning NOTES ...
Страница 264: ...264 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 4 Commissioning Notes ...
Страница 412: ...412 Rockwell Automation Publication 7000L UM301F EN P March 2020 Chapter 5 Component Definition and Maintenance ...
Страница 420: ...420 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix A Catalog Number Explanation Notes ...
Страница 428: ...428 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix C Meggering Notes ...
Страница 432: ...432 Rockwell Automation Publication 7000L UM301F EN P March 2020 Appendix D Preventative Maintenance Schedule Notes ...
Страница 433: ......