Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Terminal Block Group
(continued)
t088 [Analog Out Sel]
Related Parameter(s):
The 0…10V, 0…20 mA or 4…0 mA analog output can be used to provide a signal proportional to several drive conditions. This parameter also selects which analog
calibration parameters to use.
(1)
Values
Default:
0
Min/Max:
0/23
Display:
1
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
Options
Output Range
Minimum Output Value
Maximum Output Value =
[Analog Out High]
Filter
(1)
(1) Filter A is a single pole digital filter with a 162 ms time constant. Given a 0...100% step input from a steady state, the output of Filter A takes 500 ms to get to 95% of maximum, 810 ms to
get to 99%, and 910 ms to get to 100%.
Related
Parameter
0 “OutFreq 0-10”
0-10V
0V = 0 Hz
[Maximum Freq]
None
1 “OutCurr 0-10”
0-10V
0V = 0 A
200% Drive Rated Current
Filter A
2 “OutVolt 0-10”
0-10V
0V = 0V
120% Drive Rated Output Volts
None
3 “OutPowr 0-10”
0-10V
0V = 0 kW
200% Drive Rated Power
Filter A
4 “OutTorq 0-10”
0-10V
0V = 0 A
200% Drive Rated Current
Filter A
5 “TstData 0-10”
0-10V
0V = 0000
65535 (Hex FFFF)
None
–
6 “Setpnt 0-10”
0-10V
0V = 0%
100.0% Setpoint setting
None
7 “DCVolt 0-10”
0-10V
0V = 0V
100.0% of trip value
None
8 “OutFreq 0-20”
0-20 mA
0 mA = 0 Hz
[Maximum Freq]
None
9 “OutCurr 0-20”
0-20 mA
0 mA = 0 A
200% Drive Rated Current
Filter A
10 “OutVolt 0-20”
0-20 mA
0 mA = 0V
120% Drive Rated Output Volts
None
11 “OutPowr 0-20”
0-20 mA
0 mA = 0 kW
200% Drive Rated Power
Filter A
12 “OutTorq 0-20”
0-20 mA
0 mA = 0 A
200% Drive Rated Current
Filter A
13 “TstData 0-20”
0-20 mA
0 mA = 0000
65535 (Hex FFFF)
None
–
14 “Setpnt 0-20”
0-20 mA
0 mA = 0%
100.0% Setpoint setting
None
15 “DCVolt 0-20”
0-20 mA
0 mA = 0V
100.0% of trip value
None
16 “OutFreq 4-20”
4-20 mA
4 mA = 0 Hz
[Maximum Freq]
None
17 “OutCurr 4-20”
4-20 mA
4 mA = 0 A
200% Drive Rated Current
Filter A
18 “OutVolt 4-20”
4-20 mA
4 mA = 0V
120% Drive Rated Output Volts
None
19 “OutPowr 4-20”
4-20 mA
4 mA = 0 kW
200% Drive Rated Power
Filter A
20 “OutTorq 4-20”
4-20 mA
4 mA = 0 A
200% Drive Rated Current
Filter A
21 “TstData 4-20”
4-20 mA
4 mA = 0000
65535 (Hex FFFF)
None
–
22 “Setpnt 4-20”
4-20 mA
4 mA = 0%
100.0% Setpoint setting
None
23 “DCVolt 4-20”
4-20 mA
4 mA = 0V
100.0% of trip value
None
t089 [Analog Out High]
Scales the maximum output value (V or mA) when the source setting is at maximum.
(1)
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
t090 [Anlg Out Setpt]
Related Parameter(s):
Sets the percentage of output desired when
[Analog Out Sel] is set to 6, 14 or 22 “Analog Setpoint”.
(1)
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
(1) Parameter is also available in PowerFlex 523 FRN 3.xxx and later. PowerFlex 523 series B drive is required.
Содержание Allen-Bradley PowerFlex 520 Series
Страница 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Страница 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Страница 156: ...156 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 3 Programming and Parameters Notes ...
Страница 202: ...202 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix B Accessories and Dimensions Notes ...
Страница 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Страница 262: ...262 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix J PowerFlex 525 PM Motor Configuration Notes ...
Страница 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...