90
Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Options
43 “SherPin1 Dis”
Disables shear pin 1 but leaves shear pin 2 active. If
[Shear Pin 2 Level] is greater than 0.0 A, shear pin 2 is
enabled.
44 Reserved
45 Reserved
46 Reserved
47 Reserved
48 “2-Wire FWD”
(only for DigIn TermBlk 02)
[DigIn TermBlk 02] default. Select 2-Wire FWD for this input.
Select this option and set
[Start Source x] to 2 “DigIn TrmBlk” to
configure [Start Source x] to a 2-wire run forward mode. Also see
[2-Wire Mode]
for level trigger settings.
49 “3-Wire Start”
(only for DigIn TermBlk 02)
Select 3-Wire Start for this input.
Select this option and set
[Start Source x] to 2 “DigIn TrmBlk” to
configure [Start Source x] to a 3-wire start mode.
50 “2-Wire REV”
(only for DigIn TermBlk 03)
[DigIn TermBlk 03] default. Select 2-Wire REV for this input.
Select this option and set
[Start Source x] to 2 “DigIn TrmBlk” to
configure [Start Source x] to a 2-wire run reverse mode. Also see
[2-Wire Mode]
for level trigger settings.
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to
7 “Preset Freq”.
51 “3-Wire Dir”
(only for DigIn TermBlk 03)
Select 3-Wire Dir for this input.
Select this option and set
[Start Source x] to 2 “DigIn TrmBlk” to
change the direction of [Start Source x].
For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to
7 “Preset Freq”.
52 “Pulse Train”
(PF523: only for DigIn TermBlk 05)
(PF525: only for DigIn TermBlk 07)
Select pulse train for this input.
and
[Speed Referencex] to select pulse input.
Jumper for DigIn TermBlk 05 or 07 Sel must be moved to Pulse In.
(1) This function may be tied to one input only.
(2) Setting is specific to PowerFlex 525 drives only.
Programmable Digital Inputs (Continued)
Drive Start Condition
Matrix for t062 and
t063
t062 Setting
t063
Setting
3-Wire
Start
2-Wire
FWD
2-Wire
REV
Drive
will not
start
OK
3-Wire
Dir
OK
Drive
will not
start
t064 [2-Wire Mode]
Related Parameter(s):
Stop drive before changing this parameter.
Programs the mode of trigger only for
[DigIn TermBlk 03] when 2-wire option is being selected as
[Start Source x].
Options
0 “Edge Trigger” (Default)
Standard 2-Wire operation.
1 “Level Sense”
• I/O Terminal 01 “Stop” = Coast to stop. Drive will restart after a Stop command when:
– Stop is removed
and
– Start is held active
• I/O Terminal 03 “Run REV”
2 “Hi-Spd Edge”
• Outputs are kept in a ready-to-run state. The drive will respond to a Start command within 10 ms.
• I/O Terminal 01 “Stop” = Coast to stop.
• I/O Terminal 03 “Run REV”
3 “Momentary”
• Drive will start after a momentary input from either the Run FWD input (I/O Terminal 02) or the Run REV input (I/O
Terminal 03).
• I/O Terminal 01 “Stop” = Stop according to the value set in
[Stop Mode].
ATTENTION:
Hazard of injury exists due to unintended operation. When t064 [2-
Wire Mode] is set to option 1, and the Run input is maintained, the Run inputs do
not need to be toggled after a Stop input for the drive to run again. A Stop function
is provided only when the Stop input is active (open).
ATTENTION:
When operating in 2-Wire Level Sense (Run Level), the PowerFlex 523
and PowerFlex 525 drive should only be controlled from the Digital Input Terminal
Blocks. This should NOT be used with any other DSI or Network device.
IMPORTANT
There is greater potential voltage on the output terminals when using this
option.
Содержание Allen-Bradley PowerFlex 520 Series
Страница 8: ...8 Rockwell Automation Publication 520 UM001K EN E August 2021 Table of Contents Notes ...
Страница 68: ...68 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 2 Start Up Notes ...
Страница 156: ...156 Rockwell Automation Publication 520 UM001K EN E August 2021 Chapter 3 Programming and Parameters Notes ...
Страница 202: ...202 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix B Accessories and Dimensions Notes ...
Страница 236: ...236 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix F PID Set Up Notes ...
Страница 262: ...262 Rockwell Automation Publication 520 UM001K EN E August 2021 Appendix J PowerFlex 525 PM Motor Configuration Notes ...
Страница 270: ...270 Rockwell Automation Publication 520 UM001K EN E August 2021 Index Notes ...