Component Test Procedures
Table 5 - SCR Gate to Cathode Junction Measurements for Non-Regenerative Drives
Figure 9 - SCR Gate Lead Connection Pinouts for Non-Regenerative Drives
Check the Pulse Transformer Board
The armature pulse transformer circuit board contains an isolated gate firing
circuit and also provides dv/dt protection for the armature SCR modules. A
malfunction of these devices will be indicated by either an Overcurrent fault
(F13), blown or tripped incoming protection devices or erratic motor
operation. Use the following procedure if a malfunction in this circuitry is
suspected.
1. Read the General Safety Precautions on page
2. Remove power from the drive (see page
3. Remove the pulse transformer board (see page
).
4. With a digital multimeter set for a “continuity check”, measure each
connection point on the pulse transformer board listed in the tables
below. See
for connector locations.
If any of the actual measurements are out of tolerance, replace the pulse
transformer board (see page
On SCR Module
SCR
Measure from
To
Nominal Meter Reading
01
01
Pin 6
Pin 7
5…20 Ω
(1)
(1) The actual reading varies depending upon the SCR manufacturer. Verify that the actual measured value is consistent
for all SCRs.
04
Pin 5
Pin 4
02
02
Pin 6
Pin 7
05
Pin 5
Pin 4
03
03
Pin 6
Pin 7
06
Pin 5
Pin 4
2
1
3
2
1
3
2
1
3
SCR Module 01
SCR Module 02
SCR Module 03
Gate Lead
Pinouts
4 5
6 7
4 5
6 7
4 5
6 7
Содержание Allen-Bradley PowerFlex 20P
Страница 1: ...PowerFlex Digital DC Drive Frame B Catalog Numbers 20P Hardware Service Manual OriginalInstructions ...
Страница 8: ...8 Rockwell Automation Publication 20P TG002B EN P February 2018 Preface Notes ...
Страница 102: ...102 Rockwell Automation Publication 20P TG002B EN P February 2018 Chapter 3 Part Replacement Procedures Notes ...
Страница 128: ...128 Rockwell Automation Publication 20P TG002B EN P February 2018 Index Notes ...
Страница 129: ......