Rockwell Automation Publication 20P-TG002B-EN-P - February 2018
15
Component Test Procedures
Chapter 2
Visual Component Inspection
Visually inspect the circuit boards and power components before energizing
the drive for any of the component test procedures.
1. Read the General Safety Precautions on page
2. Remove power from the drive (see page
3. Remove the protective covers (see page
) and lower the control EMI
) when necessary.
4. Check components for burn marks, breakage or foil delamination on all
circuit boards.
Replace any of these components without further testing if they show evidence
of burn marks, breakage, or foil delamination.
Troubleshoot a Control
Power Supply Failure
If a drive Power Failure fault (F3) has occurred and the drive is inoperable via
the HIM or other means of control, compete the steps below to determine
where the control power failure has occurred.
1. Read the General Safety Precautions on page
2. Remove power from the drive (see page
3. Measure the signal voltage at the testpoints on the control board as
indicated in the following table.
Note: For a flow chart version of the steps that follow, see Control Power
Supply Failure on page
.
4. If any of the signals in the table above is incorrect or missing, verify that
either 115V AC or 230V AC voltage is present at terminals U2 and V2
(control circuit power input).
• If the voltage is present and correct, continue with step 5 below.
• If the voltage is incorrect or missing, remove control power and verify
the wiring and power source to U2, V2 and correct any problems.
Test the voltage level again to verify that it is correct. If the voltage is
correct, but the drive is still inoperable, continue with step 5 below.
Name
Testpoint For
Testpoint
Location
See…
Associated Connector-
Pin
Description
+ 5V
XY5
Figure 1
on page
17
XA-1 / XA-3 / XA-5
+5V digital supply
GNDD
XY6
Figure 1
on page
17
XA-2 / XA-4 / XA-6
+5V digital supply ground
GNDD
XY7
Figure 2
on page
18
XA-2 / XA-4 / XA-6
+5V digital supply ground
+15V
XY12
Figure 1
on page
17
XA-9 / XA-10
+15V analog supply
GNDA
XY10
Figure 1
on page
17
XA-11 / XA-12
15V analog supply ground
-15 V
XY11
Figure 1
on page
17
XA-13 / XA-14
-15V analog supply
+24V
XY8
Figure 1
on page
17
XA-16
+24V terminal block
GNDV
XY9
Figure 1
on page
17
XA-15
+24V terminal block ground
+5VEXP
+5VEXP
Figure 2
on page
18
XP3-1 / XP3-2 / XP3-3
+5V for DPI expansion
+12VEXP
+12VEXP
Figure 2
on page
18
XP3-4 / XP3-5
+12V for DPI expansion
0VEXP
0VEXP
Figure 2
on page
18
XP3-7 / XP3-8 / XP3-9
DPI expansion ground
Содержание Allen-Bradley PowerFlex 20P
Страница 1: ...PowerFlex Digital DC Drive Frame B Catalog Numbers 20P Hardware Service Manual OriginalInstructions ...
Страница 8: ...8 Rockwell Automation Publication 20P TG002B EN P February 2018 Preface Notes ...
Страница 102: ...102 Rockwell Automation Publication 20P TG002B EN P February 2018 Chapter 3 Part Replacement Procedures Notes ...
Страница 128: ...128 Rockwell Automation Publication 20P TG002B EN P February 2018 Index Notes ...
Страница 129: ......