20
Rockwell Automation Publication 20P-TG002B-EN-P - February 2018
Chapter 2
Component Test Procedures
• If any of the voltage measurements above are incorrect or missing,
continue with step 5.
• If the voltage measurements above are correct but the value of
parameter 466 [AC Line Voltage] is incorrect, replace the control
board.
5. Remove the ribbon cable connected to XR on the control board and
pulse transformer board and test the continuity of the cable using the
measurements in
on page
.
If the measurements on the XR cable are correct, replace the pulse transformer
board.
Troubleshoot an Armature
Bridge Failure
If the drive is running unstable or faults with an Overcurrent Fault (F13) an
armature bridge failure may have occurred. All of the signals going to and
coming from the SCR bridges are transmitted via the ribbon cable connected
to XR on the control board and can be measured at these points. See
for location of the XR connector on the control board.
Note: If using an AC input contactor, this step requires that the cable remain
connected to the XR connector on the control board and that an adapter be
used to measure these signals.
1. Read the General Safety Precautions on page
2. Remove the protective covers (see page
).
3. If using a DC output contactor, disconnect the cable from XR on the
control board and measure the signal for each SCR gate as indicated in
this table:
Figure 3
and
Figure 4
on page
21
, and
Figure 5
on page
22
are examples
representing gate pulse, current and voltage signal measurements taken
on an SCR. In the figures below:
– The current signal is taken on the testpoint XY17 (+2.5V offset;
+0.6V=Drive size current).
– The voltage signal is taken on the testpoint XY19 (+2.5V offset).
– The ground signal is taken on either testpoint XY10 or XY18.
Signal Name
XR Cable Pin
Gate
Note
MP
MN
IT1
27
G1
G04
IT2
29
G2
G05
IT3
31
G3
G06
IT4
21
G4 G01
IT5
23
G5
G02
IT6
25
G6
G03
MN
33
–
–
Negative bridge MN - active when high (+5V)
MP
34
–
–
Positive bridge MP - active when high (+5V)
Содержание Allen-Bradley PowerFlex 20P
Страница 1: ...PowerFlex Digital DC Drive Frame B Catalog Numbers 20P Hardware Service Manual OriginalInstructions ...
Страница 8: ...8 Rockwell Automation Publication 20P TG002B EN P February 2018 Preface Notes ...
Страница 102: ...102 Rockwell Automation Publication 20P TG002B EN P February 2018 Chapter 3 Part Replacement Procedures Notes ...
Страница 128: ...128 Rockwell Automation Publication 20P TG002B EN P February 2018 Index Notes ...
Страница 129: ......