Chapter 10
Troubleshooting the Drive
Table 21 - Fault Descriptions and Corrective Actions (Frame 3)
Fault
No
.
Ty
pe
Description
Action
AC Line Lost
227
Input power Lost, rectifier Ride Through Ena (64) is set to
Disabled.
1. Verify proper input voltage.
2. Use rectifier parameters Line Frequency (1), Input Voltage RS (7),
Input Voltage ST (8), and Input Voltage TR (9) to verify that drive can
accurately measure input frequency and voltage.
3. Check line voltage feedback signal path, including line sync board with fuse,
AC Line I/O board, and rectifier control board.
Analog In Loss
29
A user-configurable analog input is configured to fault on
signal loss. A signal loss has occurred.
Configure with inverter Analog In 1, 2 Loss (324, 327).
1. Check parameters.
2. Check for broken/loose connections at inputs.
Auto Rstrt Tries
33
Drive unsuccessfully attempted to reset a fault and
resume running for the programmed number of inverter
Auto Rstrt Tries (174).
Enable/disable with inverter Fault Config 1 (238).
Correct the cause of the fault and manually clear.
AutoTune Aborted
80
You canceled the autotune procedure.
Restart procedure.
Auxiliary Input
2
A user-configurable digital input is configured to
Aux.
Fault
and the input is open.
1. Check digital wiring.
2. Configure the digital input to something else with inverter Digital In Sel
parameter (361...366).
CarrierSync Lost
247
Rectifier could not maintain carrier synchronization to
inverter.
Configure with rectifier Fault Config (rectifier 238).
1. Set inverter PWM Frequency (inverter 151) to 4 KHz.
2. Check cabling between two control boards.
3. Replace rectifier control board.
4. Replace inverter control board.
Current Fbk Lost
35
The magnitude of motor current feedback was less than
5% of inverter Motor NP FLA (42) for the time configured
in inverter Imbalance Time (50). Detection of this fault is
disabled when inverter Imbalance Time (50) is set to the
maximum value of 10.0 seconds.
1. If motor current rating is significantly less than drive output rating, it may be
necessary to disable this fault by setting inverter Imbalance Time (50) to 10.0
seconds.
2. Verify connection of current feedback device and motor terminals.
3. If fault repeats, replace current feedback devices and/or power supply.
Decel Inhibit
24
The drive is not following a commanded deceleration
because it is attempting to limit bus voltage.
Enable/disable with inverter Fault Config 1 (238).
1. Verify input voltage is within drive specified limits.
2. Verify system ground impedance follows proper grounding techniques.
3. Disable bus regulation and/or extend deceleration time.
Drive OverLoad
64
Drive output rating of
110% for 1 minute or
150% for 5 seconds
has been exceeded.
Reduce load or extend inverter Accel Time (140, 141).
Excessive Load
79
Motor did not come up to speed in the allotted time.
1. Uncouple load from motor.
2. Repeat Autotune (inverter 61).
FluxAmpsRef Rang
78
The value for flux amps determined by the autotune
procedure exceeds the programmed inverter Motor NP
FLA (42).
1. Reprogram inverter Motor NP FLA (42) with the correct motor nameplate
value.
2. Repeat Autotune (inverter 61).
Ground Fault
13
A current path to earth ground in excess of 7% of drive
rated amps has been detected at one or more of the drive
output terminals.
Check the motor and external wiring to the drive output terminals for a
grounded condition.
See inverter Ground Current (21).
Hi Vdc Shunt
15
Drive has activated the shunt trip because the DC Bus
Voltage was above 800V DC for more than 100 ms.
1. Monitor the AC line for high line voltage or transient conditions.
2. Bus overvoltage can also be caused by motor regeneration. Extend the decel
time.
High AC Line
222
Input line voltage is too high.
Reduce input voltage to meet specification of 480 ±10%.
HW Fault
70
Inverter section of power structure hardware detected an
unexpected fault during power stage diagnostics.
Replace inverter power board.
HW OverCurrent
12
The drive output current has exceeded the hardware
current limit.
Check programming. Check for excess load, improper DC boost setting, DC brake
volts set too high or other causes of excess current.
I/O Board Fail
122
Inverter (Standard) I/O Board failure.
1. Cycle power.
2. If fault repeats, replace inverter standard I/O board.
Содержание Allen-Bradley LiquiFlo 2.0
Страница 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Страница 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Страница 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Страница 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Страница 44: ...44 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 3 Planning the Installation Notes ...
Страница 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Страница 190: ...190 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 9 Parameter Descriptions Notes ...
Страница 228: ...228 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 10 Troubleshooting the Drive Notes ...
Страница 250: ...250 Rockwell Automation Publication D2 3518 4 January 2020 Appendix A LiquiFlo 2 0 Drive Frame 3Wiring Diagrams Notes ...
Страница 258: ...258 Rockwell Automation Publication D2 3518 4 January 2020 Appendix B LiquiFlo 2 0 Drive Frame 4Wiring Diagrams Notes ...
Страница 267: ......