Rockwell Automation Publication D2-3518-4 - January 2020
195
Troubleshooting the Drive
Chapter 10
Table 18 - Types of Alarms
The drive indicates alarm conditions in the following ways:
•
Status LEDs
Determining Drive Status Using the Status LEDs on
•
Alarm name and bell graphic
). The alarm
is displayed as long as the condition exists. The drive automatically clears
the alarm when the condition causing it is removed. The OIM only
displays alarm names for type 2 alarms, not for type 1 alarms. The bell
graphic appears for both type 1 and type 2 alarms.
•
Alarm status parameters
. Two 16-bit inverter parameters, Drive Alarm 1
(211) and Drive Alarm 2 (212), indicate the status of type 1 and type 2
alarms, respectively. See
for the parameter descriptions.
•
Alarm queue
. Alarms are placed into an alarm queue on the inverter as
they occur. The alarms in the queue do not have timestamps, and there is
no indication of when each alarm becomes inactive. The queue is visible
using the OIM and using VS Utilities. The alarm queue is separate from
the inverter fault queue.
Alarm Descriptions
Type
Alarm Description
User-configurable
These alarms alert the operator of conditions that, if left untreated, may
lead to a fault condition. The drive continues to operate during the alarm
condition.
The alarms are enabled or disabled using inverter Alarm Config 1 (259).
The status of these alarms is shown in inverter Drive Alarm 1 (211).
Non-configurable
These alarms alert the operator of conditions caused by improper
programming and prevent the drive from starting until the problem is
resolved.
These alarms are always enabled.
The status of these alarms is shown in inverter Drive Alarm 2 (212).
Alarm
Ty
pe Description
Analog In Loss
A user-configurable analog input is configured for alarm on signal loss and signal loss has occurred.
Bipolar
Conflict
Parameter inverter 190 (Direction Mode) is set to Bipolar or Reverse Dis and one of more of the following digital
input functions is configured: Fwd/Rev, Run Fwd, Run Rev, Jog Fwd, or Jog Rev.
Dig In
ConflictA
User-configurable digital input functions are in conflict. Combinations marked with a
will cause an alarm.
Acc2 / Dec2 Accel 2
Decel 2
Jog
Jog Fwd
Jog Rev
Fwd / Rev
Acc2 / Dec2
Accel 2
Decel 2
Jog
Jog Fwd
Jog Rev
Fwd / Rev
Содержание Allen-Bradley LiquiFlo 2.0
Страница 1: ...LiquiFlo 2 0 AC Drive User Manual OriginalInstructions ...
Страница 6: ...6 Rockwell Automation Publication D2 3518 4 January 2020 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication D2 3518 4 January 2020 Preface Notes ...
Страница 12: ...12 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 1 Introduction Notes ...
Страница 34: ...34 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 2 About the Drive Notes ...
Страница 44: ...44 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 3 Planning the Installation Notes ...
Страница 68: ...68 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 8 Programming Basics Notes ...
Страница 190: ...190 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 9 Parameter Descriptions Notes ...
Страница 228: ...228 Rockwell Automation Publication D2 3518 4 January 2020 Chapter 10 Troubleshooting the Drive Notes ...
Страница 250: ...250 Rockwell Automation Publication D2 3518 4 January 2020 Appendix A LiquiFlo 2 0 Drive Frame 3Wiring Diagrams Notes ...
Страница 258: ...258 Rockwell Automation Publication D2 3518 4 January 2020 Appendix B LiquiFlo 2 0 Drive Frame 4Wiring Diagrams Notes ...
Страница 267: ......