64
Rockwell Automation Publication 442G-UM001B-EN-P - May 2016
Appendix A
Troubleshooting and Assistance
DIA LED Not Illuminated and State LED Not Illuminated or Does Not
Flash
Possible causes:
• Handle configuration is complete.
• DIP switch five still set to “ON” (system configuration (series or
standalone operation not fully completed).
Remedy:
• When the handle configuration is complete, the operating voltage must
then be switched off at the locking module for at least three seconds to
activate the new code of the handle assembly in the locking module. As
an alternative, 24V can be applied to the input RST for at least three
seconds.
• Complete the device configuration (see
(using DIP switches) on page 34
) process (set DIP switch five to
“OFF”). Restart the Access Box.
DIA LED Not Illuminated and State LED Flashes Three Times
The device indicates that it is ready to learn a new handle assembly. This state
will continue for three minutes after power-up with the door open.
DIA LED Not Illuminated and State LED Flashes Approximately Every
Three Seconds
The device displays normal operation with the door open. If this display also
occurs with the door close, the handle module has already been taught in and is
being blocked on this Access Box.
Remedy:
Repeat handle configuration with a new handle assembly (see
Power
State
DIA
Lock
Power
State 3 x flash
DIA
Lock
Power
State flashes approximately every 3 seconds
DIA
Lock
Содержание Allen-Bradley Guardmaster 442G-MAB B-U Series
Страница 12: ...12 Rockwell Automation Publication 440G UM001B EN P May 2016 Chapter 1 General Description Notes ...
Страница 26: ...26 Rockwell Automation Publication 440G UM001B EN P May 2016 Chapter 3 Installation and Wiring Notes ...
Страница 58: ...58 Rockwell Automation Publication 440G UM001B EN P May 2016 Chapter 6 Specifications Notes ...
Страница 66: ...66 Rockwell Automation Publication 442G UM001B EN P May 2016 Appendix A Troubleshooting and Assistance Notes ...
Страница 67: ......