Placing and Configuring the Drive
2-17
Configuring the Drive’s Response to a Connection Failure or Controller
Mode Change
The drive contains several parameters that allow you to configure the drive’s
response to communication loss to the controller. From the drive’s
perspective, a communication loss can come in the following two forms.
•
The controller closes the connection (for example, the connection is
inhibited).
•
A general failure occurs causing the connection to time out.
Parameter 386 [Lgx OutofRunCnfg] configures the drive’s response to the
controller is removed from the Run Mode. Parameter 387 [Lgx Timeout
2.
To send additional data from the drive to the controller, go to the To DriveLogix tab.
Click the button in front of the
UserDefinedRealData[0] tag
3.
Select the desired source (parameter 307 [Output Voltage] in this example) in the resulting window.
Содержание Allen-Bradley DriveLogix 5730
Страница 6: ...4 ...
Страница 10: ...p 4 Notes ...
Страница 22: ...1 12 What is DriveLogix5730 Notes ...
Страница 68: ...3 20 Placing and Configuring Local I O Notes ...
Страница 131: ...Communicating with Devices on an EtherNet IP Link 6 33 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 134: ...6 36 Communicating with Devices on an EtherNet IP Link Notes ...
Страница 155: ...Communicating with Devices on an ControlNet Link 7 21 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 182: ...9 10 Communicating with Devices on a DH485 Link Notes ...
Страница 200: ...B 10 Access Procedures Notes ...
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 209: ...Allen Bradley User Manual DriveLogix 5730 ...