7-26
Communicating with Devices on an ControlNet Link
Example 3: Total Connections Required by DriveLogix1
The following table calculates the connections used in this example.
If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.
You can configure the 1756-CNB module to use no connection. This is
useful if you configure all direct connections to their associated I/O
modules and do not need a rack-optimized connection.
Connection:
Amount:
DriveLogix1 controller to 3 local I/O modules
rack-optimized connection for the DIN rail
direct connection for each I/O module
1
3
DriveLogix1 controller to local 1788-CNC
0
DriveLogix1 controller to remote 1756-CNB
1
DriveLogix1 controller to remote ControlNet PLC-5
1
connected, cached MSG from DriveLogix1 to Control1
1
connected, cached MSG from DriveLogix1 to PLC5C1
1
Produced TagA
produced from DriveLogix1 to DriveLogix2
consumed by PLC5C1
1
1
Consumed TagB from DriveLogix2
1
Consumed INT from PLC5C1
1
total connections used: 12
Содержание Allen-Bradley DriveLogix 5730
Страница 6: ...4 ...
Страница 10: ...p 4 Notes ...
Страница 22: ...1 12 What is DriveLogix5730 Notes ...
Страница 68: ...3 20 Placing and Configuring Local I O Notes ...
Страница 131: ...Communicating with Devices on an EtherNet IP Link 6 33 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 134: ...6 36 Communicating with Devices on an EtherNet IP Link Notes ...
Страница 155: ...Communicating with Devices on an ControlNet Link 7 21 This example shows DriveLogix1 producing tagA and consuming tagB ...
Страница 182: ...9 10 Communicating with Devices on a DH485 Link Notes ...
Страница 200: ...B 10 Access Procedures Notes ...
Страница 205: ......
Страница 206: ......
Страница 207: ......
Страница 209: ...Allen Bradley User Manual DriveLogix 5730 ...