Publication 1756-UM001A-EN-P - September 2000
Route PLC-5
®
or SLC 500
™
Messages From a DH+
™
Network
14-7
D.
Select a set-up:
For a message from
a:
In this item:
Specify:
PLC-5 controller
Communication Command
PLC-5 Typed Read
or
PLC-5 Typed Write
Data Table Address (This PLC-5)
starting address of the data in the controller that sends the message
Size in Elements
number of elements to read or write
Port Number
port through which the message exits
Data Table Address (Target Device)
starting address of the data in the controller that receives the message
Local DH+ Node (Octal)
node number of the 1756-DHRIO module that is on the same network as
the controller that sends the message
Local/Remote
Remote
Remote Link Type
Data Highway
Remote Station Address
node number of the controller that receives the message
Remote Bridge Link ID
link ID of the DH+ network of the controller that receives the message
SLC 500 controller
Communication Command
PLC5 Read
or
PLC5 Write
Data Table Address (This Controller)
starting address of the data in the controller that sends the message
Size in Elements
number of elements to read or write
Channel
1
Data Table Address (Target Device)
starting address of the data in the controller that receives the message
Local Bridge Addr (octal)
node number of the 1756-DHRIO module that is on the same network as
the controller that sends the message
Remote Bridge Addr
0
Remote Station Address
node number of the controller that receives the message
Remote Bridge Link ID
link ID of the network of the controller that receives the message
Содержание Allen-Bradley ControlLogix 1756-L Series
Страница 1: ...ControlLogix System 1756 Lx User Manual ...
Страница 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Страница 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Страница 90: ...Publication 1756 UM001A EN P September 2000 6 16 Communicate with 1794 I O Over a ControlNet Network Notes ...
Страница 108: ...Publication 1756 UM001A EN P September 2000 7 18 Communicate with Another Controller over a ControlNet Network Notes ...
Страница 112: ...Publication 1756 UM001A EN P September 2000 8 4 Route PLC 5 Messages Between ControlNet Networks Notes ...
Страница 119: ...Publication 1756 UM001A EN P September 2000 Communicate with a PanelView Terminal Over a ControlNet Network 9 7 ...
Страница 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Страница 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Страница 188: ...Publication 1756 UM001A EN P September 2000 14 8 Route PLC 5 or SLC 500 Messages From a DH Network Notes ...
Страница 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Страница 232: ...Publication 1756 UM001A EN P September 2000 18 18 Configure DF1 Master and Slave Communications Notes ...
Страница 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Страница 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Страница 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Страница 305: ......
Страница 307: ...ControlLogix System User Manual ...