Appendix
A
Map a PLC/SLC Address
When To Use This
Procedure
Use this procedure if you are sending a message from a PLC-5
®
or
SLC 500
™
controller to a ControlLogix controller and the PLC/SLC
controller does not support Logical ASCII addressing.
To use a logical address (e.g., N7:0) to specify a value (tag) in a
ControlLogix controller, you must map files to tags:
•
You only have to map the file numbers that are used in
messages; the other file numbers do not need to be mapped.
•
The mapping table is loaded into the controller and is used
whenever a “logical” address accesses data.
•
You can only access controller-scoped tags (global data).
Map an Address
1.
In RSLogix 5000
™
software, open the project file for the
controller whose data you want to access.
2.
From the Logic menu, select
Map
PLC/SLC Messages
.
Содержание Allen-Bradley ControlLogix 1756-L Series
Страница 1: ...ControlLogix System 1756 Lx User Manual ...
Страница 10: ...Publication 1756 UM001A EN P September 2000 Table of Contents vi ...
Страница 64: ...Publication 1756 UM001A EN P September 2000 4 16 Communicate with 1756 I O Notes ...
Страница 90: ...Publication 1756 UM001A EN P September 2000 6 16 Communicate with 1794 I O Over a ControlNet Network Notes ...
Страница 108: ...Publication 1756 UM001A EN P September 2000 7 18 Communicate with Another Controller over a ControlNet Network Notes ...
Страница 112: ...Publication 1756 UM001A EN P September 2000 8 4 Route PLC 5 Messages Between ControlNet Networks Notes ...
Страница 119: ...Publication 1756 UM001A EN P September 2000 Communicate with a PanelView Terminal Over a ControlNet Network 9 7 ...
Страница 152: ...Publication 1756 UM001A EN P September 2000 11 4 Monitor Connections Notes ...
Страница 160: ...Publication 1756 UM001A EN P September 2000 12 8 Communicate with a DeviceNet Device Notes ...
Страница 188: ...Publication 1756 UM001A EN P September 2000 14 8 Route PLC 5 or SLC 500 Messages From a DH Network Notes ...
Страница 204: ...Publication 1756 UM001A EN P September 2000 15 16 Communicate Over a Remote I O Network Notes ...
Страница 232: ...Publication 1756 UM001A EN P September 2000 18 18 Configure DF1 Master and Slave Communications Notes ...
Страница 266: ...Publication 1756 UM001A EN P September 2000 21 10 Maintain the Battery Notes ...
Страница 286: ...Publication 1756 UM001A EN P September 2000 B 18 Estimate Execution Time Notes ...
Страница 300: ...Publication 1756 UM001A EN P September 2000 C 14 Estimate Memory Use Notes ...
Страница 305: ......
Страница 307: ...ControlLogix System User Manual ...