Rockwell Automation Publication 1512A-UM101B-EN-P - December 2021
75
Appendix A ArcShield Unit Information
Figure 59 - Cross-section of Plenum Extension, dimensions in inches [mm]
Plenum Exhaust Considerations
The following options for locating the plenum exhaust are presented:
1. Plenum ducted to an area of the control room where arc gases are
permitted to escape, with plenum extensions (see
,
and
2. Plenum duct to outside of control room (see
and
).
Plan the location where the plenum will exhaust.
•
There is no access to personnel while equipment is energized.
•
Area is free of flammable material or vapors.
Ensure that adequate space is provided around the plenum exhaust, as
outlined in
23 [584]
25 [633]
IMPORTANT
Equipment in the area of the plenum exhaust point will be
damaged or destroyed.