![Rockwell Automation Allen-Bradley CENTERLINE 2500 Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-centerline-2500/allen-bradley-centerline-2500_instruction-manual_1475204044.webp)
Publication 2500-IN001A-EN-P - May 2006
5-4
Commissioning
NOTE:
High efficiency motors may have higher locked rotor and inrush
currents. Therefore, higher magnetic trip settings may be required.
11.
Refer to the device instruction sheets or manuals supplied with the
MCC for specific start-up guidance. Set and verify adjustable current,
voltage and other settings, according to device instructions or wiring
diagrams.
Component devices in MCC units such as: transfer switches, power
factor correction capacitors, transducers, motor protectors, line
monitors, over and under-voltage relays, motor windings heaters, may
require unique start-up procedures
12.
Manually exercise all switches, control auxiliary switches, circuit
breakers, their respective operators, unit interlocks, trip mechanisms
(test by pushing the “Push to Trip” button) and any other operating
mechanisms to verify proper operation.
13.
Check timing relay settings as required.
14.
Vents and Fans
A.
Check vents to help ensure they are free from obstructions.
B.
Check fans, used for forced air cooling to help ensure the shaft
rotates freely.
C.
Check that filters are in place and clean. It is recommended to set up
an in-house program for scheduled cleaning or replacement.
15.
Check all current transformers for proper polarity. Ensure transformer
secondaries are NOT “open,” and are either connected to their
respective devices or “shorted.” Reference individual unit wiring
diagrams and schematics for proper installation.
ATTENTION
Rockwell Automation AC drives and soft starter units are
shipped with preset factory settings such as ramp speed,
current limits, switch positions, readouts, etc. Preset factory
settings may not be suitable for many applications. Refer to
instruction manuals, supplied with the MCC, for specific
startup guidance.
ATTENTION
Current transformer secondaries should not be “open.” To
avoid possible injury and electrical shock to personnel, do
not energize a current transformer with its secondary open.
Содержание Allen-Bradley CENTERLINE 2500
Страница 1: ...CENTERLINE 2500 Low Voltage Motor Control Centers Instruction Manual...
Страница 3: ...Instruction Manual CENTERLINE 2500 Motor Control Centers...
Страница 4: ......
Страница 10: ...Publication 2500 IN001A EN P May 2006 iv Notes...
Страница 18: ...Publication 2500 IN001A EN P May 2006 1 8 General Information Notes...
Страница 22: ...Publication 2500 IN001A EN P May 2006 2 4 Transporting Motor Control Centers Notes...
Страница 52: ...Publication 2500 IN001A EN P May 2006 5 12 Commissioning Notes...
Страница 82: ...Publication 2500 IN001A EN P May 2006 10 6 Maintenance Notes...
Страница 84: ...Publication 2500 IN001A EN P May 2006 11 2 Maintenance After Fault Condition Notes...
Страница 86: ...Publication 2500 IN001A EN P May 2006 12 2 Renewal Parts Notes...
Страница 87: ......